Remote boiler access lets plant staff see boiler data and alarms from anywhere, but the safety controls on a boiler have to stay local and hard-wired, lockouts have to be reset at the boiler, and the network connection has to be locked down so nobody outside the plant can change a setting. McKenna Boiler Works, Inc. installs and sets up boiler monitoring and controls, and this post covers where to draw the line between remote and on-site, and how to connect a boiler room without opening it to the internet.
What can be done remotely, and what has to happen at the boiler?
| Action | Remote? | Why |
|---|---|---|
| View status, trends, and alarms | Yes | Read-only data carries no risk to the boiler and catches problems early |
| Receive alarm emails or texts | Yes | Gets the right person moving, but someone still has to go to the boiler |
| Change a setpoint or enable a boiler | Only if your site allows it in writing, for named users | A wrong setpoint can short-cycle a boiler or starve a process |
| Reset a flame safeguard lockout | No; at the boiler | The cause has to be found first, and repeated resets can leave unburned fuel in the furnace |
| Start a cold boiler | No; at the boiler with an operator present | Water level, warm-up rate, and the flame have to be watched |
| Bypass or adjust a safety limit | Never, from anywhere | Low water cutoffs, limits, and the flame safeguard are the last line of protection |
Whether a boiler may run without an operator in attendance depends on the boiler, its controls, your insurer, and the rules in your jurisdiction. Check with Cal/OSHA and your insurance inspector before changing how a boiler is attended.
Why must the safety controls stay hard-wired?
On a properly built boiler, the low water cutoff, auxiliary low water cutoff, high pressure or high temperature limit, gas pressure switches, combustion air proving switch, and flame safeguard are wired in series in the safety circuit. When any one opens, power to the fuel valves is removed directly. That circuit does not depend on a PLC, a BMS, a gateway, or a network, so a software bug, a lost connection, or a bad command cannot keep fuel flowing when a limit has tripped.
ASME CSD-1 covers controls and safety devices on automatically fired boilers under 12.5 MMBtu/hr input, and NFPA 85 covers boilers at 12.5 MMBtu/hr and above. NFPA 85 requires the burner management system logic to be independent of, or isolated from, the boiler’s other control logic. When monitoring is added to an existing boiler, it should read from the controls and never be wired into the safety circuit. McKenna sets up remote monitoring as monitoring only.
What are the cyber risks for a boiler room?
- No authentication in industrial protocols. Modbus, common on burner controls and gateways, has no built-in login. Any device that can reach it on the network can read registers, and write them if writes are enabled.
- Devices exposed to the internet. A gateway or controller given a public address can be found by internet scanning tools.
- Default and shared passwords. Factory passwords left in place, or one login shared by everyone, make it impossible to know who changed what.
- Vendor access left open. A remote connection set up for one service call and never closed.
With the safety circuit hard-wired, the realistic harm is a changed setpoint, a boiler disabled, or nuisance shutdowns: lost production and a cold building. That is reason enough to lock it down.
How do you connect a boiler room safely?
- Segment the network. Put boiler controls and gateways on their own network segment behind a firewall, separate from office computers and guest Wi-Fi.
- Keep devices off the public internet. Remote users connect through a VPN or a managed remote access service with multi-factor authentication.
- Make it read-only where you can. Disable Modbus writes unless a documented need exists, and list every writable point.
- Give each person their own login. Change default passwords at commissioning. Remove access the day an employee or contractor leaves.
- Log remote sessions so changes can be traced.
- Update firmware on the schedule the manufacturer recommends.
- Bring in your IT department before the gateway is connected, so it follows the plant’s security policy.
McKenna installs and sets up burners and controls from any manufacturer and can work with your IT staff on the connection.
Who gets the alarms, and what do they do?
An alarm is only useful if someone acts on it. Write an alarm plan: which alarms go to whom, who backs them up on nights and weekends, and what each person does. For a lockout or low water alarm, the answer is the same: someone goes to the boiler, finds the cause, and follows the site procedure. Remote data helps the technician arrive with the right parts. Operators should be trained on both the alarms and the on-site response; see boiler operator training.
What to check on an existing remote connection
- Is the gateway or controller reachable from the public internet? If so, close it.
- Are default passwords still in place?
- Who has accounts, and does each person still need one?
- Which points are writable, and is that written down?
- Is anything from the monitoring system wired into the safety circuit? If so, have it corrected.
- Do daily checks still happen at the boiler: gauge glass, low water cutoff test, and walk-around? Follow the manufacturer’s instructions, lockout/tagout, and site procedures. If a low water cutoff does not shut the burner off during a test, shut the burner off manually and call for service.
Common questions
Should boiler controls share a network with office computers?
No. Put boiler controls and gateways on their own segment behind a firewall. A virus or a misconfigured device on the office network then cannot reach the boiler controls directly.
Is it safe to let the BMS change boiler setpoints?
It can be, if the safety circuit is hard-wired and the writable points are limited, documented, and restricted to named users. Many plants keep the boiler connection read-only and change setpoints at the controller.
Does Modbus have security built in?
No. Standard Modbus has no login or encryption, so security comes from the network around it: segmentation, a firewall, a VPN with multi-factor authentication, and disabling writes that are not needed.
How should we give a contractor remote access?
Give the contractor a named account with multi-factor authentication, limited to the devices they service. Turn the access on for the job and off when it ends, and keep a log of the session.
Does remote monitoring change inspection or testing requirements?
No. Cal/OSHA inspections, ASME CSD-1 safety control testing, and the manufacturer’s test schedule still apply. Monitoring helps you see trends between those visits.
McKenna sets up boiler monitoring that reads data without touching the safety circuit, and installs controls from any manufacturer. To review or add remote access, see remote monitoring or call (323) 987-1816.