Boiler Room Remote Monitoring with the Autoflame Mk8 DTI

boiler maintenance men monitoring boiler room on laptop

The Autoflame Mk8 DTI (Data Transfer Interface) is a gateway that collects data from the Autoflame burner controls in a boiler room, logs it, sends alarm emails, and passes the data to a building management system (BMS) or a PC on the plant network. McKenna Boiler Works, Inc. is a factory-authorized Autoflame Tech Center and installs and commissions the DTI on new and existing boilers. The DTI is a monitoring tool: the low water cutoffs, limits, and flame safeguard on each boiler stay local and hard-wired, and McKenna sets it up that way.

What does the Mk8 DTI connect to?

The DTI sits one level above the burner controllers. Each boiler fitted with an Autoflame Mk8 MM (micro-modulation) controller, or with a Mini Mk8 MM already in service, positions its own fuel and air servos and knows its firing rate, setpoint, actual steam pressure or water temperature, burner status, and lockout history. The DTI reads that information from every controller and puts the whole plant on one screen.

DeviceCapacity in Autoflame’s Mk8 DTI manualWhat it adds to the picture
Mk8 MM controllers, and Mini Mk8 MM controllers already in serviceUp to 10, in any combinationFiring rate, setpoint and actual value, servo positions, burner status, lockouts and alarms
Mk8 EGA exhaust gas analyzersUp to 10Flue gas O2, CO, CO2, and exhaust temperature, plus NO where the analyzer has that cell
Input/output modulesUp to 10Analog and digital points from other plant equipment, such as feedwater tank level, condensate temperature, makeup water meter pulses, and pump run status
Mk8 gas and air pressure sensorsUp to 10, in any combinationHeader or line pressure trends

Ask for the current Autoflame data sheet when you plan a system, because capacities and features can change between product revisions.

How does the data get out of the boiler room?

  • Touchscreen. The DTI’s own screen shows each boiler’s status in real time, so an operator can see the whole plant from one spot.
  • Modbus to a BMS. Modbus over RS422 and Ethernet is standard. Your controls contractor maps the Modbus registers into the BMS or plant SCADA. If the BMS speaks BACnet only, a protocol gateway is usually added.
  • DTI Manager software. Collects data to a PC over the local network or the internet for trending and reports.
  • Alarm emails. The DTI sends a network email when a fault or alarm occurs, so the right people hear about a lockout without standing in front of the boiler.
  • Logged history. Autoflame’s Mk8 DTI manual describes up to three years of boiler house data stored on board, with I/O module and pressure sensor logs kept for two years. That lets you compare this winter with last winter at the same firing rate.

A BMS can also send commands through the DTI when it is configured to allow it, for example a setpoint change or enabling a boiler. Decide up front which points, if any, are writable and who may change them, and write that down. In a correctly wired system the low water cutoffs, high limit, gas pressure switches, air proving switch, and flame safeguard sit in the hard-wired safety circuit, so no command over the network can bypass them.

What should a plant engineer trend?

Raw numbers mean little until you compare them at the same firing rate over time. These are the trends that point to a real problem early:

  • Stack temperature at a given firing rate. A slow rise means heat is not getting into the water. On the fireside that is soot; on the waterside it is scale, which insulates the tube so more heat leaves up the stack. The U.S. Department of Energy’s steam tip sheets give a rule of thumb: boiler efficiency rises about 1 percent for every 40°F reduction in flue gas temperature.
  • O2 at a given firing rate. Drift away from the commissioned value points to a change in fuel pressure, combustion air temperature, a slipping servo coupling, or a fouled burner. It is the cue for a combustion tuning visit.
  • Burner starts per hour. Many starts on light load means short cycling. Each start adds a purge that cools the furnace and stresses the refractory and tube joints. Setpoint and differential changes, lead-lag settings, or more turndown can fix it.
  • Lockout and alarm history. Repeated flame failures on the same boiler at the same time of day are a pattern worth chasing: a weak pilot, a dirty scanner, or a gas pressure dip when another load starts.
  • Run hours per boiler. Use them to rotate the lead boiler so wear is shared.
  • Makeup water and feedwater tank level. A rising makeup trend, read from an I/O module, means lost condensate, leaks, or steam traps blowing through.

What does the DTI not do?

  • It does not replace the daily walk-around, the gauge glass check, or the low water cutoff test. Those happen at the boiler, under ASME CSD-1 testing and the manufacturer’s instructions.
  • It does not reset a lockout safely from the office. A lockout should be reset by a person at the boiler who has found the cause.
  • It does not replace the annual inspection or the Cal/OSHA permit to operate.
  • It does not calibrate itself. An EGA needs its own calibration, and an annual tune with a calibrated portable analyzer still applies.

What to check after a DTI is installed

  1. Every boiler appears on the touchscreen with the right name, and its status matches what you see at the boiler.
  2. DTI readings match local gauges: steam pressure, water temperature, and O2 against a portable analyzer.
  3. Test the alarm email path with a non-safety test input on an I/O module. Do not create a real low water or flame failure to test email. Test safety controls separately, following the manufacturer’s instructions, lockout/tagout where required, and your site’s procedures.
  4. Keep the email recipient list current. Update it the day someone leaves or changes shifts.
  5. Document every Modbus point mapped to the BMS, and mark which ones are writable.
  6. Put the DTI on a segmented plant network, change default passwords, and do not expose it directly to the internet.
  7. Train operators on what each alarm means and who goes to the boiler when it comes in. McKenna offers boiler operator training.

Common questions

Do I need Autoflame burner controls to use the Mk8 DTI?

Yes. The DTI reads Autoflame Mk8 MM controllers, Mini Mk8 MM controllers already in service, and Mk8 EGAs. Basic points from boilers with other controls can come in through I/O modules, or those boilers can be monitored through their own system. McKenna installs and sets up burners and controls from any manufacturer.

Can the DTI start, stop, or reset a boiler?

The DTI can pass certain commands from a BMS, such as a setpoint change or enabling a boiler, if it is configured to allow them. Lockout resets belong at the boiler, done by someone who has found the cause. The safety limits are hard-wired and cannot be overridden through the DTI.

How much history does the DTI keep?

Autoflame’s Mk8 DTI manual describes up to three years of boiler house data stored on board, with I/O module and pressure sensor logs kept for two years. If you need longer records for your own reporting, export the data to the BMS or a PC on a schedule.

Can the DTI connect to our building management system?

Modbus over RS422 and Ethernet is standard, so most BMS platforms can read it once the registers are mapped. If your BMS only uses BACnet, a protocol gateway is typically added between the two.

Does the DTI replace the annual combustion tune?

No. The DTI shows when O2 or stack temperature drifts, which helps you schedule the tune. The tune itself is done at the burner with a calibrated analyzer, and the curves are reset by a trained technician.

McKenna installs, commissions, and services the Autoflame Mk8 DTI as a factory-authorized Autoflame Tech Center, and installs, sets up, and tunes burners and controls from any manufacturer. To add a DTI to your boiler room or connect it to your BMS, see remote monitoring or call (323) 987-1816.

Need help with your boiler? McKenna Boiler Works, Inc. builds, installs, and services industrial boilers across California, and services and repairs other brands. Call (323) 987-1816 or request service.

Firetube boiler tubesheet with the old tubes removed during a McKenna retube

Retube or Replace a Firetube Boiler: How to Decide

Leaking or thinning tubes do not always mean a new boiler. Here is how to decide between a retube and

Read article →

Welding at a firetube boiler tubesheet

Boiler R Stamp Repair: What It Involves and When You Need One

Replacing tubes or welding on a shell, tubesheet, furnace, or nozzle is code work under the National Board Inspection Code.

Read article →

McKenna feedwater tank on a stand with duplex feed pumps below and water softeners beside it

Water Treatment and Its Impact on Industrial Boiler Reliability

Scale, oxygen pitting, and carbonic acid shorten boiler life. How each mechanism works, what a treatment program includes, and who

Read article →