<?xml version="1.0" encoding="UTF-8"?><rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:wfw="http://wellformedweb.org/CommentAPI/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
	xmlns:slash="http://purl.org/rss/1.0/modules/slash/"
	>

<channel>
	<title>McKenna Boiler</title>
	<atom:link href="https://www.mckennaboiler.com/feed/" rel="self" type="application/rss+xml" />
	<link>https://www.mckennaboiler.com/</link>
	<description>Turnkey industrial boiler systems, engineered and built in California.</description>
	<lastBuildDate>Mon, 16 Nov 2026 17:11:32 +0000</lastBuildDate>
	<language>en-US</language>
	<sy:updatePeriod>
	hourly	</sy:updatePeriod>
	<sy:updateFrequency>
	1	</sy:updateFrequency>
	<generator>https://wordpress.org/?v=7.1.5</generator>

<image>
	<url>https://www.mckennaboiler.com/wp-content/uploads/2026/07/cropped-mckenna-flame-site-icon-32x32.jpg</url>
	<title>McKenna Boiler</title>
	<link>https://www.mckennaboiler.com/</link>
	<width>32</width>
	<height>32</height>
</image> 
	<item>
		<title>Retube or Replace a Firetube Boiler: How to Decide</title>
		<link>https://www.mckennaboiler.com/boiler-repair/retube-or-replace-boiler/</link>
		
		<dc:creator><![CDATA[McKenna Boiler Team]]></dc:creator>
		<pubDate>Fri, 06 Nov 2026 10:47:50 +0000</pubDate>
				<category><![CDATA[Boiler Repair]]></category>
		<guid isPermaLink="false">https://www.mckennaboiler.com/?p=999180</guid>

					<description><![CDATA[<p>Leaking or thinning tubes do not always mean a new boiler. Here is how to decide between a retube and a replacement based on the pressure vessel, emissions limits, and load.</p>
<p>The post <a href="https://www.mckennaboiler.com/boiler-repair/retube-or-replace-boiler/">Retube or Replace a Firetube Boiler: How to Decide</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></description>
										<content:encoded><![CDATA[<p>Retube a firetube boiler when the shell, tubesheets, and furnace are sound and the boiler still fits the load and can meet its emissions limit. Replace it when the pressure vessel itself is worn, the load has changed, or a retube plus the burner work needed to meet current NOx rules costs close to a new boiler. On an inspection, McKenna Boiler Works, Inc. gives you two numbers, the cost to repair and upgrade the boiler you have and the cost of a new McKenna boiler.</p>
<h2>How do you know the tubes are failing?</h2>
<p>Tubes are the thinnest pressure parts in a firetube boiler and usually the first to go. Watch for these signs:</p>
<ul>
<li>Leaks at the tube ends. Weeping at the tubesheet, wet soot, or water at the tube ends or in the furnace after a shutdown.</li>
<li>Tube failures in service. A split or ruptured tube forces a shutdown.</li>
<li>Pitting. Oxygen pitting on the water side, from dissolved oxygen in the feedwater or poor layup while the boiler sits idle.</li>
<li>Scale. Scale insulates the tube, so the metal runs hotter than it should. It also shows up as a rising stack temperature.</li>
<li>Thinning on ultrasonic testing (UT). Thickness readings that approach or fall below what the inspector will accept.</li>
</ul>
<p>One failed tube does not mean every tube is bad. A pattern of failures, or thinning across many tubes on UT, usually does.</p>
<p>Common causes of tube failure include scale or sludge that insulates the tube so the metal overheats, oil or grease in the boiler water, oxygen pitting from dissolved oxygen, low water, cold water added to a warm boiler, fast warm-ups and short cycling, and electrolysis (galvanic corrosion). Follow the water quality guidelines in your boiler manufacturer’s manual, and work with your water treatment company to build a program around them. McKenna is not a water treatment company. Your water treatment company should be on site during the inspection to check and monitor the water side. Fix the cause first, or new tubes will fail the same way.</p>
<h2>What does a retube involve?</h2>
<p>A retube replaces all of the fire tubes in the boiler. In most cases, replacing rolled and beaded tubes is not an R stamp repair; confirm with your Authorized Inspector. When the tubes are seal welded or the work involves welding on the tubesheet, it is an R stamp repair under NBIC Part 3, made by a National Board R certificate holder and documented on Form R-1. The basic sequence:</p>
<ol>
<li>Shut down, cool, drain, and open the boiler. Open the front and rear doors and pull the burner if needed.</li>
<li>Remove the old tubes. Cut them, collapse the ends, and pull them out.</li>
<li>Inspect the tubesheets. Clean the tube holes and check them for size, cracks between holes (ligament cracks), and corrosion. Inspect the furnace and shell while the boiler is open.</li>
<li>Install the new tubes. Each tube is expanded (rolled) into the tubesheets, then beaded, seal welded, or both, to match the boiler&#8217;s design and its code of construction. Seal welded tubes are rolled again after welding.</li>
<li>Hydrostatic test. The boiler is filled and pressure tested, with the Authorized Inspector witnessing when the repair or your jurisdiction requires it.</li>
<li>Close out. Replace door gaskets and refractory as needed, complete the R-1 if the work was an R stamp repair, and return the boiler to service.</li>
</ol>
<p>Downtime depends on boiler size, tube count, and how fast tubes and materials arrive. The tubesheet inspection matters most. If the tubesheets or furnace have problems, the scope grows, and that can change the decision.</p>
<h2>When does a retube make sense?</h2>
<p>A retube is a good investment when the rest of the boiler is in good shape. Check these points before you commit:</p>
<ul>
<li>Shell, tubesheets, and furnace. A retube does not replace these. Ligament cracks, a bulged or distorted furnace, or thinning in the shell can make a retube a poor investment.</li>
<li>Age and history. An older boiler with a clean history can be worth retubing. One with repeated weld repairs to the pressure vessel may not be.</li>
<li>Efficiency. New tubes restore heat transfer lost to scale and fouling, but they do not change the boiler&#8217;s design. If the design is inefficient, a retube will not fix it.</li>
<li>Emissions limits. In the South Coast AQMD, Rules 1146, 1146.1, and 1146.2 set NOx limits by boiler size, and the limits have come down over time. Rule 1146.2, which covers units of 2 million Btu/hr and smaller, now phases in zero-emission requirements. Other California air districts have their own rules. A retube does not change NOx. If the burner cannot meet the current limit, the usual options are an <a href="/services/ultra-low-nox-retrofits/">ultra-low NOx retrofit</a> or a new boiler. Check the current rule and your permit before you decide.</li>
<li>Burner and controls. If the burner and controls are near the end of their life, add that cost to the retube number.</li>
<li>Parts availability. If parts for the burner, controls, or boiler are no longer available, every future repair takes longer.</li>
<li>Load. If your steam or hot water demand has changed, the boiler may be oversized and short cycling, or undersized and running flat out. A retube keeps the same capacity.</li>
</ul>
<h2>How does a retube compare with a new boiler?</h2>
<table>
<thead>
<tr>
<th></th>
<th>Retube</th>
<th>New boiler</th>
</tr>
</thead>
<tbody>
<tr>
<td>Downtime</td>
<td>The boiler is out of service for the whole job. Length depends on tube count, inspection findings, and material lead time.</td>
<td>The new boiler is built while the old one keeps running, if it can. Downtime covers removal, installation, and startup. A McKenna <a href="/rentals/">rental boiler</a> can carry the load.</td>
</tr>
<tr>
<td>Scope</td>
<td>Replace fire tubes, inspect tubesheets, furnace, and shell, hydro test.</td>
<td>Remove the old boiler, set the new one, connect piping, fuel, and controls, start up and tune.</td>
</tr>
<tr>
<td>What it fixes</td>
<td>Leaking, pitted, scaled, or thin tubes. Restores heat transfer.</td>
<td>The pressure vessel, burner, controls, efficiency, emissions, and sizing to the current load.</td>
</tr>
<tr>
<td>What it does not fix</td>
<td>Shell, furnace, or tubesheet damage. An old burner and controls. NOx compliance. A boiler sized wrong for the load.</td>
<td>Poor water treatment. A new boiler still needs a water treatment program.</td>
</tr>
<tr>
<td>Paperwork</td>
<td>Form R-1 under NBIC Part 3 when the retube is an R stamp repair (seal-welded tubes or tubesheet welding).</td>
<td>New ASME Manufacturer&#8217;s Data Report, permit to operate, and air permit as required.</td>
</tr>
<tr>
<td>Upfront cost</td>
<td>Lower.</td>
<td>Higher.</td>
</tr>
</tbody>
</table>
<h2>When does replacement make more sense?</h2>
<p>Replace the boiler when the pressure vessel is the problem, when a retube plus a burner and controls upgrade gets close to the cost of a new boiler, or when the boiler no longer fits the load or the emissions rule.</p>
<p>McKenna builds <a href="/equipment/firetube-boilers/">firetube</a>, firebox, and vertical boilers in its own ASME shop in California, as standard models or custom-designed to your specifications and to fit the room. New boilers come with Autoflame controls as a standard option and a burner matched to the boiler and the emissions limit. McKenna handles the <a href="/services/boiler-replacement/">boiler replacement</a>, installation, and startup in Los Angeles and across California, and does startup and commissioning in any state.</p>
<h2>How to decide between a retube and a new boiler</h2>
<p>Start with an <a href="/services/boiler-inspections-testing/">inspection</a>. Have the boiler opened and the tubes and tubesheets inspected. If you need UT thickness readings on the tubes and shell, McKenna can prepare a proposal for them. Review the burner, the controls, and the air permit at the same time.</p>
<p>Then get both numbers. On an inspection, McKenna gives you the cost to repair and upgrade the boiler you have, and the cost of a new McKenna boiler. Compare them over the years you expect to run the equipment. Include the upfront price, fuel, maintenance, expected downtime, and what it will take to meet the NOx limit.</p>
<p>When a retube involves welding, such as seal-welded tubes or tubesheet repairs, McKenna makes that R stamp repair under its National Board R certificate, on boilers and pressure vessels from any manufacturer.</p>
<h2>Schedule a retube inspection</h2>
<p>If your tubes are leaking or your last inspection flagged thinning, see McKenna&#8217;s <a href="/services/boiler-retubes/">boiler retube service</a>. Call (323) 987-1816 to schedule an inspection.</p>
<h2>Common questions</h2>
<h3>How long does a firetube boiler retube take?</h3>
<p>It depends on the boiler size, the number of tubes, and how quickly tubes and materials arrive. Problems found on the tubesheets or furnace can add time. Plan the shutdown with some margin and arrange backup steam or heat if you have no redundant boiler.</p>
<h3>Is a boiler retube a code repair?</h3>
<p>In most cases, replacing rolled and beaded tubes is not an R stamp repair; check with your Authorized Inspector before the work starts. When the tubes are seal welded or the work involves welding on the tubesheet or other pressure parts, it is an R stamp repair under NBIC Part 3, made by a National Board R certificate holder, inspected by an Authorized Inspector, and documented on Form R-1. Your Authorized Inspector can confirm what your jurisdiction requires before the work starts.</p>
<h3>Will retubing lower my NOx emissions?</h3>
<p>No. NOx is set mainly by the burner, how it is tuned, and the furnace it fires into. New tubes do not change it. If your burner cannot meet your air district&#8217;s current limit, the usual options are an ultra-low NOx burner retrofit or a new boiler. Check the current rule for your unit size first.</p>
<h3>How do I know if my tubesheets are still good?</h3>
<p>A visual inspection and UT readings with the boiler open give a first look. The full check happens with the tubes out, when the tube holes can be checked for size, cracks between holes, and corrosion. If the tubesheets need major repair, compare that cost with a new boiler before you go ahead.</p>
<p><script type="application/ld+json">{"@context":"https://schema.org","@type":"FAQPage","mainEntity":[{"@type":"Question","name":"How long does a firetube boiler retube take?","acceptedAnswer":{"@type":"Answer","text":"It depends on the boiler size, the number of tubes, and how quickly tubes and materials arrive. Problems found on the tubesheets or furnace can add time. Plan the shutdown with some margin and arrange backup steam or heat if you have no redundant boiler."}},{"@type":"Question","name":"Is a boiler retube a code repair?","acceptedAnswer":{"@type":"Answer","text":"In most cases, replacing rolled and beaded tubes is not an R stamp repair; check with your Authorized Inspector before the work starts. When the tubes are seal welded or the work involves welding on the tubesheet or other pressure parts, it is an R stamp repair under NBIC Part 3, made by a National Board R certificate holder, inspected by an Authorized Inspector, and documented on Form R-1. Your Authorized Inspector can confirm what your jurisdiction requires before the work starts."}},{"@type":"Question","name":"Will retubing lower my NOx emissions?","acceptedAnswer":{"@type":"Answer","text":"No. NOx is set mainly by the burner, how it is tuned, and the furnace it fires into. New tubes do not change it. If your burner cannot meet your air district's current limit, the usual options are an ultra-low NOx burner retrofit or a new boiler. Check the current rule for your unit size first."}},{"@type":"Question","name":"How do I know if my tubesheets are still good?","acceptedAnswer":{"@type":"Answer","text":"A visual inspection and UT readings with the boiler open give a first look. The full check happens with the tubes out, when the tube holes can be checked for size, cracks between holes, and corrosion. If the tubesheets need major repair, compare that cost with a new boiler before you go ahead."}}]}</script></p>
<p>The post <a href="https://www.mckennaboiler.com/boiler-repair/retube-or-replace-boiler/">Retube or Replace a Firetube Boiler: How to Decide</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>Boiler R Stamp Repair: What It Involves and When You Need One</title>
		<link>https://www.mckennaboiler.com/boiler-repair/boiler-r-stamp-repair/</link>
		
		<dc:creator><![CDATA[McKenna Boiler Team]]></dc:creator>
		<pubDate>Fri, 06 Nov 2026 10:47:50 +0000</pubDate>
				<category><![CDATA[Boiler Repair]]></category>
		<guid isPermaLink="false">https://www.mckennaboiler.com/?p=999179</guid>

					<description><![CDATA[<p>Replacing tubes or welding on a shell, tubesheet, furnace, or nozzle is code work under the National Board Inspection Code. Here is what a National Board R stamp repair involves, who inspects it, and how to plan one.</p>
<p>The post <a href="https://www.mckennaboiler.com/boiler-repair/boiler-r-stamp-repair/">Boiler R Stamp Repair: What It Involves and When You Need One</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></description>
										<content:encoded><![CDATA[<p>A boiler R stamp repair is welding or other code work on the pressure parts of a boiler or pressure vessel, done under the National Board Inspection Code (NBIC) by a company that holds a National Board R Certificate of Authorization. You typically need one when you weld on a shell, tubesheet, or furnace, replace seal-welded tubes, or repair a nozzle on a code-stamped boiler or vessel, though the exact rules depend on your jurisdiction. In most cases, replacing rolled and beaded tubes is not an R stamp repair; check with your Authorized Inspector. McKenna Boiler Works, Inc. holds National Board R Certificate No. 11037 and makes code repairs on boilers and pressure vessels from any manufacturer.</p>
<h2>Is the work a repair or an alteration?</h2>
<p>ASME Section I covers how power boilers are built, and ASME Section IV covers heating boilers. Once a boiler is in service, repairs and alterations follow the NBIC in jurisdictions that adopt it. NBIC Part 3 covers repairs and alterations.</p>
<p>A repair restores the boiler to a safe operating condition without changing its design. Replace a seal-welded tube, weld a corroded area back to thickness, or cut out and replace a cracked section, and the boiler still matches its original Manufacturer&#8217;s Data Report.</p>
<p>An alteration changes the design. Raising the maximum allowable working pressure (MAWP) or temperature, increasing heating surface or steaming capacity enough to need more relieving capacity, or adding an opening that needs reinforcement are all alterations. An alteration needs design calculations, and the paperwork is different.</p>
<p>The line between the two is not always obvious. A new nozzle can be a repair or an alteration depending on its size and whether it needs reinforcement. The Inspector, and in some cases the jurisdiction, makes that call, so ask before the job is scoped.</p>
<h2>What work counts as a code repair?</h2>
<p>If the work welds on a pressure-retaining part, or replaces one that is welded in place, treat it as a code repair until your inspector says otherwise. Common examples:</p>
<ul>
<li>Replacing seal-welded tubes, or a <a href="/services/boiler-retubes/">retube</a> that involves welding on the tubesheet.</li>
<li>Welded repairs to shells, tubesheets, and furnaces, such as building up pitted or corroded areas or replacing a cracked section.</li>
<li>Nozzle work, such as replacing a corroded nozzle, repairing a nozzle weld, or replacing a flange on a pressure connection.</li>
<li>Stay and staybolt replacement on firebox boilers.</li>
<li>Weld repairs to code-stamped tanks and pressure vessels, such as air receivers and blowdown tanks.</li>
</ul>
<p>Work that does not touch the pressure boundary, such as burner tuning, controls, refractory, gaskets, and cleaning, is maintenance. Some jurisdictions let certain routine repairs go ahead without prior inspector acceptance, but they still have to be documented. Check with your jurisdiction.</p>
<h2>Who inspects a code repair?</h2>
<p>Every code repair has a third party checking it. The Authorized Inspector (AI) holds a National Board commission and works for an Authorized Inspection Agency (AIA) or for the jurisdiction. Every R certificate holder must keep an inspection agreement with an AIA, and the inspector on a repair normally comes through that agreement. On a repair, the AI:</p>
<ul>
<li>Accepts the repair method before work starts.</li>
<li>Checks that the welding procedures and welders are qualified, normally under ASME Section IX.</li>
<li>Inspects the work in progress and the finished repair.</li>
<li>Witnesses the pressure test when one is required.</li>
<li>Signs the repair report.</li>
</ul>
<p>The jurisdiction is the state or local authority that issues your permit to operate. In California, that is the Cal/OSHA Pressure Vessel Unit, and California&#8217;s boiler safety orders set their own repair rules, including which repairs need a qualified inspector&#8217;s approval before work starts. The jurisdiction sets its own rules on which repairs need notice, when an inspection is due after a repair, and how reports are filed. Rules differ from state to state, so confirm them before you plan the job.</p>
<h2>How is a code repair documented?</h2>
<p>When a repair is finished, the R certificate holder completes Form R-1, Report of Repair. It describes the boiler or vessel, the work done, the materials used, the pressure test, and who did and inspected the work. The certificate holder and the AI both sign it.</p>
<p>An alteration is documented on Form R-2, Report of Alteration. It covers both the design and the construction side of the change, and design calculations back up any new rating.</p>
<p>The repaired item is also marked. The certificate holder applies a stamping or nameplate near the original nameplate showing the R symbol, its certificate number, and the date. After an alteration that changes the rating, the new rating goes on the nameplate as well. Some jurisdictions waive the stamping for routine repairs, so ask yours.</p>
<p>Copies of the report go to the owner and the jurisdiction. If the boiler is registered with the National Board, the report can be registered too.</p>
<h2>What records should the owner keep?</h2>
<p>Keep a file for each boiler and pressure vessel for the life of the equipment. It should hold:</p>
<ul>
<li>The original Manufacturer&#8217;s Data Report and the National Board number, if the item is registered.</li>
<li>Every R-1 and R-2 report, in date order.</li>
<li>Inspection reports and the current permit to operate.</li>
<li>Pressure test records and nondestructive examination (NDE) results, such as ultrasonic thickness readings.</li>
<li>Water treatment logs from your water treatment company.</li>
</ul>
<p>This file matters at the next inspection, when you sell or move the equipment, and when you have to decide whether to repair or replace. A boiler with a complete repair history is easier to evaluate than one with gaps.</p>
<h2>How to plan a code repair</h2>
<p>Most code repairs can be planned. Tube leaks, pitting, and cracked welds often show up at an annual inspection before they cause a forced outage. Planning around that gives you the most control over downtime.</p>
<ol>
<li>Schedule the shutdown. Pick a window when the load is lowest. Allow time to cool down, drain, and open the boiler, and for the inspection before the repair starts.</li>
<li>Inspect first. An <a href="/services/boiler-inspections-testing/">internal inspection</a> with the boiler open sets the scope. Your water treatment company sets the chemical program and should be on site during the inspection to check and monitor the water side, because many pressure-part failures trace back to water chemistry.</li>
<li>Get the repair method accepted. The R certificate holder writes up the repair, and the AI accepts it before any welding.</li>
<li>Order materials. Replacement tubes, plate, and fittings have to meet the original code requirements. Material lead time can set the schedule.</li>
<li>Plan for backup steam or heat. If you have no redundant boiler, a McKenna <a href="/rentals/">rental boiler</a> can carry the load during the repair. Arrange it early so it is on site and connected before the shutdown.</li>
<li>Test and close out. The AI witnesses the hydrostatic test if one is required, the R-1 is signed, and the boiler goes back in service.</li>
</ol>
<p>If a failure forces an unplanned shutdown, the same steps apply on a shorter timeline. McKenna handles <a href="/services/emergency-services/">emergency boiler repairs</a> for that situation.</p>
<h2>Who can make a code repair?</h2>
<p>Under the NBIC, code repairs are made by a company holding a National Board R Certificate of Authorization, and that company completes and signs Form R-1. Some jurisdictions accept other arrangements for certain work, so confirm what yours requires. Each certificate has a scope. McKenna&#8217;s covers metallic repairs and alterations at shop and field locations, so the work can be done at your plant or in McKenna&#8217;s shop in Oceanside, California.</p>
<p>McKenna also holds ASME S, H, M, and U certificates for building new boilers and pressure vessels, and maintains a written quality control manual for its code work. McKenna makes code repairs on boilers and pressure vessels from any manufacturer under its National Board R certificate, in Los Angeles and across California.</p>
<h2>Schedule an R stamp repair</h2>
<p>If an inspection turned up a code repair, or you are planning a shutdown, see McKenna&#8217;s <a href="/services/r-stamp-repair/">National Board R stamp repair service</a>. Call (323) 987-1816 to schedule the work.</p>
<h2>Common questions</h2>
<h3>What is the difference between a National Board R certificate and an ASME certificate?</h3>
<p>ASME certificates such as S, H, and U cover building new boilers and pressure vessels. The National Board R certificate covers repairs and alterations to equipment already in service, under the NBIC. Under the NBIC, code repairs are made by an R certificate holder, which completes and signs Form R-1.</p>
<h3>Does replacing boiler tubes require an R stamp?</h3>
<p>In most cases, replacing rolled and beaded tubes is not an R stamp repair; check with your Authorized Inspector before the work starts. When the tubes are seal welded, or the job involves welding on the tubesheet or other pressure parts, it is an R stamp repair: an R certificate holder does the work, an Authorized Inspector inspects it, and it is documented on Form R-1.</p>
<h3>Who is the Authorized Inspector on a repair?</h3>
<p>The Authorized Inspector holds a National Board commission and works for an Authorized Inspection Agency or for the jurisdiction. Every R certificate holder must keep an inspection agreement with an Authorized Inspection Agency, and the inspector on the repair normally comes through that agreement. Bring the inspector in early, because the repair method has to be accepted before work starts.</p>
<h3>Can an R stamp repair be done on site?</h3>
<p>Yes, if the certificate holder&#8217;s scope includes field work. McKenna&#8217;s National Board R certificate covers metallic repairs and alterations at shop and field locations. Smaller vessels and parts can also be repaired in the shop.</p>
<h3>What paperwork should I get after a code repair?</h3>
<p>Get a copy of the signed Form R-1, or Form R-2 for an alteration, plus any pressure test and NDE records. Check that the stamping or nameplate was applied near the original nameplate if your jurisdiction requires it. File everything with the boiler&#8217;s Manufacturer&#8217;s Data Report and inspection history.</p>
<p><script type="application/ld+json">{"@context":"https://schema.org","@type":"FAQPage","mainEntity":[{"@type":"Question","name":"What is the difference between a National Board R certificate and an ASME certificate?","acceptedAnswer":{"@type":"Answer","text":"ASME certificates such as S, H, and U cover building new boilers and pressure vessels. The National Board R certificate covers repairs and alterations to equipment already in service, under the NBIC. Under the NBIC, code repairs are made by an R certificate holder, which completes and signs Form R-1."}},{"@type":"Question","name":"Does replacing boiler tubes require an R stamp?","acceptedAnswer":{"@type":"Answer","text":"In most cases, replacing rolled and beaded tubes is not an R stamp repair; check with your Authorized Inspector before the work starts. When the tubes are seal welded, or the job involves welding on the tubesheet or other pressure parts, it is an R stamp repair: an R certificate holder does the work, an Authorized Inspector inspects it, and it is documented on Form R-1."}},{"@type":"Question","name":"Who is the Authorized Inspector on a repair?","acceptedAnswer":{"@type":"Answer","text":"The Authorized Inspector holds a National Board commission and works for an Authorized Inspection Agency or for the jurisdiction. Every R certificate holder must keep an inspection agreement with an Authorized Inspection Agency, and the inspector on the repair normally comes through that agreement. Bring the inspector in early, because the repair method has to be accepted before work starts."}},{"@type":"Question","name":"Can an R stamp repair be done on site?","acceptedAnswer":{"@type":"Answer","text":"Yes, if the certificate holder's scope includes field work. McKenna's National Board R certificate covers metallic repairs and alterations at shop and field locations. Smaller vessels and parts can also be repaired in the shop."}},{"@type":"Question","name":"What paperwork should I get after a code repair?","acceptedAnswer":{"@type":"Answer","text":"Get a copy of the signed Form R-1, or Form R-2 for an alteration, plus any pressure test and NDE records. Check that the stamping or nameplate was applied near the original nameplate if your jurisdiction requires it. File everything with the boiler's Manufacturer's Data Report and inspection history."}}]}</script></p>
<p>The post <a href="https://www.mckennaboiler.com/boiler-repair/boiler-r-stamp-repair/">Boiler R Stamp Repair: What It Involves and When You Need One</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>Water Treatment and Its Impact on Industrial Boiler Reliability</title>
		<link>https://www.mckennaboiler.com/boilers/water-treatment-and-its-impact-on-industrial-boiler-reliability/</link>
		
		<dc:creator><![CDATA[McKenna Boiler Team]]></dc:creator>
		<pubDate>Wed, 04 Nov 2026 18:52:49 +0000</pubDate>
				<category><![CDATA[Boiler Maintenance]]></category>
		<category><![CDATA[Boilers]]></category>
		<guid isPermaLink="false">https://www.mckennaboiler.com/uncategorized/water-treatment-and-its-impact-on-industrial-boiler-reliability/</guid>

					<description><![CDATA[<p>Scale, oxygen pitting, and carbonic acid shorten boiler life. How each mechanism works, what a treatment program includes, and who is responsible for what, from operators to the water treatment company.</p>
<p>The post <a href="https://www.mckennaboiler.com/boilers/water-treatment-and-its-impact-on-industrial-boiler-reliability/">Water Treatment and Its Impact on Industrial Boiler Reliability</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></description>
										<content:encoded><![CDATA[<p>Feedwater and boiler water chemistry decide how long the pressure parts of an industrial boiler last. Hardness forms scale that drives tube and furnace metal temperatures up, dissolved oxygen pits steel, carbon dioxide corrodes condensate lines, and concentrated solids cause carryover and deposits. McKenna Boiler Works, Inc. is not a water treatment company: your water treatment company sets the program, and McKenna inspects, maintains, and repairs the boiler that program protects.</p>
<figure><img decoding="async" src="/wp-content/uploads/2026/11/mckenna-tank-feedwater-tank-on-stand-food-plant.webp" alt="McKenna feedwater tank on a stand with duplex feed pumps below and water softeners beside it"></figure>
<h2>What does scale do to a firetube boiler?</h2>
<p>Calcium and magnesium hardness, and silica, come in with the makeup water. Calcium carbonate and calcium sulfate become less soluble as water gets hotter, so they come out of solution on the hottest surfaces first: the furnace and the first-pass tubes. As water boils off as steam, the minerals left behind keep concentrating.</p>
<p>Scale conducts heat poorly. The burner&#8217;s heat still has to pass through the steel and then the scale to reach the water, so the steel runs hotter to push the same heat through. In the furnace, where heat flux is highest, that can overheat the metal enough to bulge the furnace or crack tube ends. Stack temperature also rises, because less heat is absorbed, and fuel use goes up. Loose sludge settles at the bottom of the shell, where bottom blowdown removes it.</p>
<h2>How do oxygen and carbon dioxide cause corrosion?</h2>
<p>Dissolved oxygen attacks steel at local spots and forms pits. Pitting is the dangerous kind of corrosion because it goes deep in a small area, and a pit can go through a tube wall while the rest of the tube looks fine. It is worst where oxygenated water first meets hot steel: the feedwater line, the feed connection, and tubes near it. Oxygen comes out of water as it heats, so the first defense is mechanical. A deaerator heats feedwater to saturation and vents the released gases, and a hot feedwater tank removes part of the oxygen. An oxygen scavenger, usually sodium sulfite, removes what is left. Operators test the sulfite residual to confirm there is enough.</p>
<p>Carbon dioxide comes from bicarbonate and carbonate alkalinity in the makeup water. In the boiler these break down and release CO2, which leaves with the steam and dissolves in the condensate as carbonic acid. That acid thins condensate piping and eats threads, usually along the bottom of the pipe. The controls are reducing alkalinity in the makeup water and neutralizing amines chosen by the water treatment company.</p>
<p>Caustic gouging is a third mechanism. Where deposits are porous or steam blankets a surface, boiler water concentrates under the deposit and caustic attacks the steel underneath. Keeping deposits off the heating surface and alkalinity in range prevents it. Idle boilers corrode too, so lay up any boiler that sits as the boiler manufacturer&#8217;s manual specifies, with your water treatment company setting the chemistry.</p>
<h2>What does a treatment program include?</h2>
<table>
<thead>
<tr>
<th>Control</th>
<th>What it does</th>
<th>Who handles it</th>
</tr>
</thead>
<tbody>
<tr>
<td>Water softener</td>
<td>Removes hardness from makeup water by ion exchange</td>
<td>Operators regenerate and test; the program sets the hardness limit</td>
</tr>
<tr>
<td>Deaerator or hot feedwater tank</td>
<td>Drives out dissolved oxygen and CO2 by heating</td>
<td>Operators hold the temperature and keep vents working</td>
</tr>
<tr>
<td>Oxygen scavenger</td>
<td>Removes remaining oxygen chemically</td>
<td>Water treatment company sets the residual; operators test</td>
</tr>
<tr>
<td>Internal treatment and dispersants</td>
<td>Keeps hardness leakage and iron in suspension so blowdown can remove them</td>
<td>Water treatment company</td>
</tr>
<tr>
<td>Surface (continuous) blowdown</td>
<td>Holds dissolved solids and conductivity in range</td>
<td>Operators or automatic controls, to the program&#8217;s limits</td>
</tr>
<tr>
<td>Bottom blowdown</td>
<td>Removes sludge from the bottom of the boiler</td>
<td>Operators, on the program&#8217;s schedule</td>
</tr>
<tr>
<td>Condensate treatment</td>
<td>Neutralizes carbonic acid in return lines</td>
<td>Water treatment company</td>
</tr>
</tbody>
</table>
<p>Blowdown is a balance. The boiler manufacturer&#8217;s manual gives the blowdown limits for your boiler, and your water treatment company sets the rate from your water analysis. Too little blowdown lets solids build up and causes foaming and carryover. Too much wastes hot, treated water and fuel. Returning more condensate lowers the solids coming in, so less blowdown is needed. Blowdown is hot and under pressure, so it goes to a <a href="/equipment/blowdown-tanks/">blowdown tank or separator</a> to cool before the drain, as local codes require.</p>
<p>For guidance on limits by operating pressure, many programs refer to the ASME consensus document on operating practices for feedwater and boiler water chemistry in industrial and institutional boilers, first published as CRTD-34. It is guidance. Start with the water limits in your boiler manufacturer&#8217;s manual, and work with your water treatment company to set the limits for your boiler.</p>
<h2>Who is responsible for what?</h2>
<ul>
<li>Your water treatment company sets the program around the boiler manufacturer&#8217;s guidelines, chooses the chemicals, sets test limits and frequencies, reviews the logs, and should be on site during inspections to check and monitor the water side while the boiler is open.</li>
<li>Your operators run the daily tests, log them, blow down on schedule, regenerate the softener, hold feedwater temperature, and report readings that are out of range.</li>
<li>The boiler service company opens and cleans the boiler, inspects the fire side and water side, and repairs damage. Welded repairs to pressure-retaining parts are made under the National Board Inspection Code (NBIC) Part 3 by an organization holding a National Board R certificate, and accepted by an Authorized Inspector. In most cases, replacing rolled and beaded tubes is not an R stamp repair; check with your Authorized Inspector. McKenna holds National Board R certificate No. 11037 and makes <a href="/services/r-stamp-repair/">code repairs</a> on boilers and pressure vessels from any manufacturer.</li>
</ul>
<p>Under Cal/OSHA rules, power boilers are inspected internally and externally each year, by a Cal/OSHA safety engineer or a certified inspector, before the permit to operate is renewed. When the Division considers a longer interval between internal inspections, water treatment records are part of what it reviews.</p>
<h2>What to check: an operator&#8217;s water-side routine</h2>
<ul>
<li>Test softened water hardness, boiler water conductivity, and sulfite residual each day the boiler runs, or as the program says, and log every result.</li>
<li>Hold the <a href="/equipment/feedwater-systems/">feedwater tank</a> at the temperature the program calls for.</li>
<li>Blow down on the schedule your water treatment company sets, and never less often than the boiler manufacturer&#8217;s manual calls for. Open bottom blowdown valves slowly, in the order the manufacturer specifies, watch the gauge glass, and never leave an open blowdown valve unattended. Follow your site&#8217;s procedures.</li>
<li>Read the makeup water meter daily. A rise means condensate is being lost or there is a leak.</li>
<li>Before an inspection, shut the boiler down and let it cool and lose all pressure before it is drained, following the manufacturer&#8217;s instructions. Apply lockout/tagout to fuel, electrical, and water, isolate the steam, feedwater, and blowdown lines, and follow confined space procedures for any entry. Ask your water treatment company to be on site.</li>
<li>Review the inspection findings with your water treatment company. Scale, pitting, or deposits mean the program needs adjusting.</li>
</ul>
<h2>Common questions</h2>
<h3>How often should boiler water be tested?</h3>
<p>Your water treatment program sets the schedule. For most steam boilers in service, operators test softener hardness, conductivity, and scavenger residual daily, and the water treatment company runs fuller tests on its visits.</p>
<h3>Is softened water enough?</h3>
<p>No. A softener removes hardness only. Oxygen, carbon dioxide, alkalinity, and silica still have to be handled by deaeration, chemicals, and blowdown.</p>
<h3>Do hot water boilers need treatment?</h3>
<p>Yes. A closed hot water loop uses little makeup, but it still needs a corrosion inhibitor, and rising makeup in a closed loop points to a leak that brings in fresh oxygen and hardness.</p>
<h3>Does McKenna provide water treatment?</h3>
<p>No. McKenna Boiler Works, Inc. is not a water treatment company. Your water treatment company sets the chemical program and should be on site during inspections, and McKenna inspects, maintains, and repairs the boiler.</p>
<h3>What happens if scale is found during an inspection?</h3>
<p>The inspector may require cleaning before the boiler returns to service, and damaged tubes or furnace sections may need repair, with welded repairs made under NBIC Part 3. Your water treatment company should find the cause and adjust the program so it does not return.</p>
<p>To schedule an annual inspection with the boiler opened for the water side, see <a href="/services/boiler-inspections-testing/">boiler inspections and testing</a> or call (323) 987-1816.</p>
<p>The post <a href="https://www.mckennaboiler.com/boilers/water-treatment-and-its-impact-on-industrial-boiler-reliability/">Water Treatment and Its Impact on Industrial Boiler Reliability</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>Emergency Boiler Rentals: What to Do When a Boiler Fails</title>
		<link>https://www.mckennaboiler.com/boiler-rental/emergency-and-temporary-boiler-rentals-keep-your-facility-running/</link>
		
		<dc:creator><![CDATA[McKenna Boiler Team]]></dc:creator>
		<pubDate>Fri, 30 Oct 2026 09:22:00 +0000</pubDate>
				<category><![CDATA[Boiler Rental]]></category>
		<guid isPermaLink="false">https://www.mckennaboiler.com/uncategorized/emergency-and-temporary-boiler-rentals-keep-your-facility-running/</guid>

					<description><![CDATA[<p>When a boiler fails and the repair will take time, a rental can carry the load. Here is what to make safe first, what information sizes the rental, and what permits and connections it needs.</p>
<p>The post <a href="https://www.mckennaboiler.com/boiler-rental/emergency-and-temporary-boiler-rentals-keep-your-facility-running/">Emergency Boiler Rentals: What to Do When a Boiler Fails</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></description>
										<content:encoded><![CDATA[<p>When a boiler fails and the repair will take days or weeks, a rental boiler can carry the steam or hot water load while the permanent unit is repaired, retubed, or replaced. McKenna Boiler Works, Inc. has rental boilers for this, and how fast one runs at your plant depends mostly on two things: how much McKenna knows about your load on the first call, and how ready your connection points are when the truck arrives.</p>
<figure class="wp-block-image size-full"><img fetchpriority="high" decoding="async" width="340" height="200" src="/wp-content/uploads/2024/09/commercial-boiler-for-rent-los-angeles.jpg" alt="Commercial rental boiler" class="wp-image-17427" srcset="https://www.mckennaboiler.com/wp-content/uploads/2024/09/commercial-boiler-for-rent-los-angeles.jpg 340w, https://www.mckennaboiler.com/wp-content/uploads/2024/09/commercial-boiler-for-rent-los-angeles-300x176.jpg 300w" sizes="(max-width: 340px) 100vw, 340px" /></figure>
<h2>What should happen in the first hours after a boiler fails?</h2>
<p>Make the failed boiler safe before anyone thinks about a rental. If the failure involves low water and the level is out of sight in the gauge glass, shut the burner off and do not add feedwater to a hot boiler. Cold water on overheated tubes and tube sheets can crack them or loosen tube ends, and a dry-fired boiler has to be inspected before it is refilled. If the flame safeguard has locked out, do not keep resetting it; repeated restarts can put unburned fuel in the furnace. Follow the manufacturer&#8217;s instructions and your site&#8217;s lockout/tagout procedure for the burner, fuel, and electrical supply.</p>
<p>Next, sort the loads. Most plants have a few loads that cannot stop (sterilizers, a cook kettle line, domestic hot water in a hospital, building heat in cold weather) and others that can wait. A rental sized for the critical loads arrives and connects faster than one sized for the whole plant, and you may already have a second boiler that can carry part of the load while the rental is set.</p>
<h2>What information sizes an emergency rental?</h2>
<p>A rental has to match the steam pressure or water temperature your equipment needs and carry the load at that condition. Load is usually stated in pounds of steam per hour (lb/hr), boiler horsepower, or thousand Btu per hour (MBH). One boiler horsepower is 33,475 Btu/hr, or 34.5 lb/hr of steam from and at 212°F, so a 200 hp boiler is roughly 6,900 lb/hr from and at 212°F. The <a href="/equipment/boiler-sizing-calculator/">boiler sizing calculator</a> converts between these units.</p>
<table>
<thead>
<tr>
<th>Item</th>
<th>Why it matters</th>
<th>Where to find it</th>
</tr>
</thead>
<tbody>
<tr>
<td>Operating pressure or supply water temperature</td>
<td>Sets the rental&#8217;s pressure rating and safety valve setting</td>
<td>Boiler data plate, operating log, process equipment specs</td>
</tr>
<tr>
<td>Load to carry (lb/hr, hp, or MBH)</td>
<td>Sets rental size; undersizing drops pressure, oversizing short-cycles</td>
<td>Failed boiler rating, steam meter, fuel meter readings</td>
</tr>
<tr>
<td>Fuel and gas pressure at the tie-in</td>
<td>The burner needs its rated supply pressure at full fire flow</td>
<td>Gas meter and regulator tag, utility account</td>
</tr>
<tr>
<td>Electrical service (voltage, phase, amps)</td>
<td>Burner blower, feedwater pumps, controls</td>
<td>Panel schedule near the boiler room</td>
</tr>
<tr>
<td>Feedwater, condensate, and makeup water</td>
<td>Decides whether the rental uses your feedwater system or brings its own</td>
<td>Feedwater tank and pump nameplates</td>
</tr>
<tr>
<td>Placement and access</td>
<td>Truck route, crane or forklift, distance to tie-in points, stack clearance</td>
<td>Site plan, photos of the yard or dock</td>
</tr>
</tbody>
</table>
<h2>What permits apply to a rental boiler in California?</h2>
<p>The customer is responsible for all permits for a rental boiler. Two agencies matter. Cal/OSHA&#8217;s Boiler and Fired Pressure Vessel Safety Orders (Title 8) require inspection and a permit to operate for power boilers, which in practice means steam boilers above 15 psig; low-pressure boilers are exempt from the annual inspection and permit under 8 CCR 771 as long as their controls are fitted and kept working. Confirm with McKenna how the rental&#8217;s inspection status applies at your site before it fires.</p>
<p>The local air district is the second. Some McKenna rental boilers carry South Coast AQMD permits, which can shorten the path inside the South Coast AQMD area: all of Orange County, the non-desert parts of Los Angeles, Riverside, and San Bernardino Counties, and the Coachella Valley. In the San Joaquin Valley, the Bay Area, and other districts, check the district&#8217;s rules for temporary or portable units before the rental runs, and read any permit conditions on fuel, location, and hours.</p>
<h2>How is a rental tied in and started?</h2>
<p>The tie-in can be done by your plant crew, your mechanical contractor, or McKenna. Whoever does it, the rental connects at points you choose ahead of time: a steam header or hot water supply and return, a gas line with an isolation valve, electrical power, feedwater or makeup water, and a drain for blowdown. Blowdown water leaves a steam boiler at saturation temperature, so it goes to a <a href="/equipment/blowdown-tanks/">blowdown tank or separator</a> that cools it before it reaches the drain; plumbing codes and local sewer rules limit discharge temperature.</p>
<p>Two details are easy to miss under pressure. First, the failed boiler must be isolated so the rental cannot backfeed it while crews work on it: closed and locked steam stop valves, the non-return or check valve where one is fitted, and a lockout on its fuel and power. Second, the rental needs treated water from the first hour. Your water treatment company sets the program and should set up chemical feed and testing for the rental, since untreated makeup water can start scaling or pitting a rental boiler quickly.</p>
<p>McKenna does the <a href="/services/commissioning-startup/">startup and commissioning</a>: verifying the low water cutoffs and flame safeguard, checking the safety valve setting against the system, and tuning combustion to the air permit limit.</p>
<h2>What to do: emergency rental checklist</h2>
<ol>
<li>Make the failed boiler safe: burner off, fuel and power locked out per your site&#8217;s procedures, no feedwater added to a boiler that ran low.</li>
<li>List the loads that cannot stop and the pressure or temperature each one needs.</li>
<li>Pull the failed boiler&#8217;s data plate rating and the last few days of log readings.</li>
<li>Photograph the yard or dock where a trailer could sit, and the route in.</li>
<li>Find the nearest gas line, electrical panel, steam header, and feedwater connection to that spot.</li>
<li>Call your water treatment company so treatment is ready when the rental fills.</li>
<li>Call (323) 987-1816 with that information in hand. A live person answers 24/7.</li>
<li>Before the rental fires, confirm the failed boiler is isolated and tagged, and that the air permit and Cal/OSHA status are settled.</li>
</ol>
<h2>Common questions</h2>
<h3>How fast can a rental boiler be running?</h3>
<p>It depends on rental availability for your pressure and size, distance, permits, and how ready the connection points are. Plants that have tie-in points already planned connect much faster than plants that start from scratch. Have the checklist information ready on the first call.</p>
<h3>Can a rental carry the whole plant?</h3>
<p>Sometimes. Rentals come in fixed sizes, and a large plant may need more than one unit, or a rental sized for critical loads while a second permanent boiler carries the rest. Sizing to the real load, measured from fuel or steam meters, avoids renting more capacity than you can connect.</p>
<h3>Does a rental boiler need its own air permit?</h3>
<p>It needs to be covered by an air district permit or exemption where it runs. Some McKenna rental boilers carry South Coast AQMD permits. Outside that district, check your district&#8217;s rules for temporary units before the rental fires.</p>
<h3>Who is responsible for water treatment on a rental?</h3>
<p>Your water treatment company sets the program for the rental the same way it does for your permanent boiler. Ask them to be ready when the rental fills, and keep testing and logging while it runs. McKenna is not a water treatment company.</p>
<h3>Should we plan a rental before anything fails?</h3>
<p>Yes. Choosing a location, tie-in points, and the needed size ahead of time removes most of the delay in an emergency. A plant that will also need a rental for a scheduled retube or replacement can use the same plan for both.</p>
<h2>Getting a rental started</h2>
<p>For rental availability, sizes, and which units carry South Coast AQMD permits, see <a href="/rentals/">McKenna rental boilers</a> and <a href="/services/emergency-services/">emergency boiler service</a>, or call (323) 987-1816. A live person answers 24/7.</p>
<p>The post <a href="https://www.mckennaboiler.com/boiler-rental/emergency-and-temporary-boiler-rentals-keep-your-facility-running/">Emergency Boiler Rentals: What to Do When a Boiler Fails</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>Industrial Boiler Maintenance Checklist for Facility Managers</title>
		<link>https://www.mckennaboiler.com/boiler-maintenance/the-industrial-boiler-maintenance-checklist-every-facility-manager-needs/</link>
		
		<dc:creator><![CDATA[McKenna Boiler Team]]></dc:creator>
		<pubDate>Wed, 14 Oct 2026 14:41:00 +0000</pubDate>
				<category><![CDATA[Boiler Maintenance]]></category>
		<guid isPermaLink="false">https://www.mckennaboiler.com/uncategorized/the-industrial-boiler-maintenance-checklist-every-facility-manager-needs/</guid>

					<description><![CDATA[<p>An industrial boiler maintenance program has two lists: what operators check every shift and week, and what a qualified technician does once a year. This checklist covers both, with the California rules behind them.</p>
<p>The post <a href="https://www.mckennaboiler.com/boiler-maintenance/the-industrial-boiler-maintenance-checklist-every-facility-manager-needs/">Industrial Boiler Maintenance Checklist for Facility Managers</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></description>
										<content:encoded><![CDATA[<p>An industrial boiler maintenance program splits into two lists: what the operator checks every shift, week, and month, and what a qualified technician does at least once a year with the boiler off line. McKenna Boiler Works, Inc. builds and services industrial boilers, and the checklist below is the one McKenna would want a facility manager to have on the boiler room wall. Your boiler manufacturer&#8217;s instructions, your insurer, and your site&#8217;s procedures come first wherever they differ.</p>
<figure class="aligncenter size-full"><img decoding="async" width="300" height="158" src="/wp-content/uploads/2021/02/boiler-services-300x158-1.jpg" alt="Industrial boiler inspection" class="wp-image-16365"/></figure>
<h2>What rules set the maintenance requirements?</h2>
<p>Three sets of rules shape a California boiler program. ASME CSD-1 covers controls and safety devices on automatically fired boilers with fuel input up to 12.5 million Btu per hour; NFPA 85 covers burner management on larger units. Both expect the safety controls to be tested on a schedule and the results recorded. Cal/OSHA&#8217;s Boiler and Fired Pressure Vessel Safety Orders (Title 8) require power boilers (steam above 15 psig) to be inspected internally and externally at least once a year under Labor Code 7682, with a permit to operate issued after inspection; the Division can extend the internal interval up to 36 months in some cases. Low-pressure boilers are exempt from the annual inspection and permit under 8 CCR 771, but only if their required automatic controls are fitted and kept working. Your air district permit adds combustion and record-keeping conditions, under South Coast AQMD Rules 1146, 1146.1, and 1146.2, San Joaquin Valley Rules 4306 and 4320, or Bay Area Regulation 9, Rule 7, depending on where the boiler is and its size.</p>
<h2>What should operators check every shift and every week?</h2>
<p>The point of daily checks is to catch a change. A boiler that needs more blowdown, burns more gas for the same load, or runs a higher stack temperature than last month is telling you something about the fire side or the water side.</p>
<table>
<thead>
<tr>
<th>Frequency</th>
<th>Check</th>
<th>What it tells you</th>
</tr>
</thead>
<tbody>
<tr>
<td>Every shift</td>
<td>Gauge glass level, steam pressure or water temperature, stack temperature, burner firing rate, alarms</td>
<td>Normal operation; a rising stack temperature at the same firing rate points to soot or scale</td>
</tr>
<tr>
<td>Every shift</td>
<td>Blow down the gauge glass and water column, per the manufacturer</td>
<td>Clear connections so the glass shows true level</td>
</tr>
<tr>
<td>Daily or weekly, per the control manufacturer</td>
<td>Blow down the float-type low water cutoff and confirm the burner stops</td>
<td>The cutoff works and its chamber is not filling with sludge</td>
</tr>
<tr>
<td>Daily</td>
<td>Water tests per your water treatment program; surface and bottom blowdown as the program sets</td>
<td>Dissolved solids, hardness, and treatment levels within the program&#8217;s limits</td>
</tr>
<tr>
<td>Weekly</td>
<td>Look for leaks at valves, flanges, manways and handholes, and the fuel train; listen to pumps and the blower</td>
<td>Small leaks found before they cut seats or gaskets</td>
</tr>
<tr>
<td>Monthly</td>
<td>Review the log for trends in fuel use, makeup water, and stack temperature</td>
<td>Rising makeup water means lost condensate or a leak</td>
</tr>
</tbody>
</table>
<p>Water treatment belongs to your water treatment company. They set the program, the test limits, and the blowdown rate within the limits in the boiler manufacturer’s manual, and they should be on site when the boiler is opened for inspection to check and monitor the water side.</p>
<figure class="wp-block-image size-full"><img decoding="async" width="800" height="816" src="/wp-content/uploads/2024/09/los-angeles-boiler-co-feedwater-system.jpg" alt="Boiler feedwater system" class="wp-image-17215" srcset="https://www.mckennaboiler.com/wp-content/uploads/2024/09/los-angeles-boiler-co-feedwater-system.jpg 800w, https://www.mckennaboiler.com/wp-content/uploads/2024/09/los-angeles-boiler-co-feedwater-system-294x300.jpg 294w, https://www.mckennaboiler.com/wp-content/uploads/2024/09/los-angeles-boiler-co-feedwater-system-768x783.jpg 768w, https://www.mckennaboiler.com/wp-content/uploads/2024/09/los-angeles-boiler-co-feedwater-system-700x714.jpg 700w" sizes="(max-width: 800px) 100vw, 800px" /></figure>
<h2>What does a qualified technician do once a year?</h2>
<p>The annual service is where the boiler gets opened, measured, and tuned. Before any door or cover is opened, the boiler is shut down, cooled, depressurized, and locked out per your site&#8217;s procedures, and nobody enters it without your confined space entry program. On most industrial firetube boilers it includes:</p>
<ul>
<li><strong>Fire-side inspection:</strong> open the front and rear doors, check tubes, tube ends, the furnace, and refractory; brush tubes if soot is present.</li>
<li><strong>Water-side inspection:</strong> remove manway and handhole covers, look for scale, sludge, pitting, and caustic gouging, and clean as needed. This is usually timed with the Cal/OSHA or insurance inspection.</li>
<li><strong>Safety control testing:</strong> primary and auxiliary low water cutoffs (including an evaporation or slow-drain test where the manufacturer calls for one), high limit and operating controls, flame safeguard and scanner, fuel valve proving, combustion air and gas pressure switches.</li>
<li><strong>Combustion analysis and tuning:</strong> measure O2, CO, NOx where required, and stack temperature across the firing range, then set the fuel and air curve to meet the air permit limit. See <a href="/services/combustion-tuning/">combustion tuning</a>.</li>
<li><strong>Safety valves:</strong> inspect, and test or replace on the interval your insurer and the valve manufacturer set. Only a qualified repair organization may adjust or repair a safety valve.</li>
<li><strong>Feedwater and blowdown equipment:</strong> pumps, check valves, the feedwater tank, and the blowdown tank or separator.</li>
</ul>
<h2>What to do: the operator&#8217;s rules</h2>
<ol>
<li>Never bypass, jumper, or disable a low water cutoff, flame safeguard, or limit to keep production running.</li>
<li>When you test a low water cutoff and the burner does not stop, shut the burner off manually, keep it off, and call for service.</li>
<li>If water is out of sight in the gauge glass, shut off the burner and do not add feedwater to a hot boiler. Call for service.</li>
<li>Follow lockout/tagout and the manufacturer&#8217;s instructions before opening any door, cover, or fuel component.</li>
<li>Keep a written log of every test and reading. Inspectors and CSD-1 expect it, and it shows trends.</li>
<li>Welded repairs on the pressure boundary (shell, tube sheets, nozzles, seal-welded tubes) are made only by an organization holding a National Board R certificate, with an Authorized Inspector accepting the repair under the NBIC. In most cases, replacing rolled and beaded tubes is not an R stamp repair; check with your Authorized Inspector.</li>
<li>Book the annual inspection and service months ahead, and fix last year&#8217;s findings first.</li>
</ol>
<h2>Common questions</h2>
<h3>How often should an industrial boiler be serviced?</h3>
<p>Operators check it every shift and log it. A qualified technician services it at least once a year, with combustion tuning and safety control testing. Boilers with heavy load swings, high run hours, or tight air permit limits may need more frequent tuning; your permit and the manufacturer set the minimum.</p>
<h3>Does Cal/OSHA inspect every boiler every year?</h3>
<p>Power boilers, meaning steam boilers above 15 psig, are inspected internally and externally at least yearly under Labor Code 7682, though the Division can extend the internal interval in some cases. Low-pressure boilers are exempt from the annual inspection and permit under 8 CCR 771 if their required controls are fitted and maintained. Check how your boiler is classified.</p>
<h3>Who should test the low water cutoff?</h3>
<p>Operators blow down float-type cutoffs on the schedule the control manufacturer sets and confirm the burner stops. The full test, including an evaporation test where called for, is done by a qualified technician during service. If a cutoff does not trip, shut the burner off manually and call for service.</p>
<h3>What records should we keep?</h3>
<p>A daily log of levels, pressures, temperatures, and blowdowns; water test results from your treatment program; safety control test results; combustion analysis reports; and inspection certificates. Air districts often require combustion and fuel records as permit conditions.</p>
<h3>Does McKenna service boilers it did not build?</h3>
<p>Yes. McKenna services and repairs boilers from other manufacturers and installs, sets up, and tunes burners and controls from any manufacturer. Code repairs on boilers and pressure vessels are made under McKenna&#8217;s National Board R certificate.</p>
<h2>Setting up a maintenance program</h2>
<p>McKenna can set up the annual work as a <a href="/services/preventative-maintenance/">preventative maintenance</a> visit or an <a href="/services/annual-service-contracts/">annual service contract</a>, timed with your <a href="/services/boiler-inspections-testing/">boiler inspection</a>. To schedule, call (323) 987-1816.</p>
<p>The post <a href="https://www.mckennaboiler.com/boiler-maintenance/the-industrial-boiler-maintenance-checklist-every-facility-manager-needs/">Industrial Boiler Maintenance Checklist for Facility Managers</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>Welding Boilers and Pressure Vessels to Code</title>
		<link>https://www.mckennaboiler.com/boilers/welding-the-critical-role-it-plays-in-pressure-vessel-and-industrial-boiler-fabrication/</link>
		
		<dc:creator><![CDATA[McKenna Boiler Team]]></dc:creator>
		<pubDate>Wed, 07 Oct 2026 22:44:58 +0000</pubDate>
				<category><![CDATA[Boiler Repair]]></category>
		<category><![CDATA[Boilers]]></category>
		<guid isPermaLink="false">https://www.mckennaboiler.com/uncategorized/welding-the-critical-role-it-plays-in-pressure-vessel-and-industrial-boiler-fabrication/</guid>

					<description><![CDATA[<p>A code weld needs a qualified procedure, a qualified welder, code materials, the right examination, and an Authorized Inspector. How that works for new construction and for repairs under NBIC Part 3.</p>
<p>The post <a href="https://www.mckennaboiler.com/boilers/welding-the-critical-role-it-plays-in-pressure-vessel-and-industrial-boiler-fabrication/">Welding Boilers and Pressure Vessels to Code</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></description>
										<content:encoded><![CDATA[<p>A weld on a boiler or pressure vessel is code-acceptable when it is made to a qualified welding procedure by a qualified welder, in code materials, examined the way the construction code requires, and accepted by an Authorized Inspector. New construction falls under ASME Section I, IV, or VIII, and weld repairs to equipment in service fall under the National Board Inspection Code (NBIC) Part 3. McKenna Boiler Works, Inc. holds ASME S, H, M, and U certificates and a National Board R certificate, and maintains a written quality control manual for its code work.</p>
<figure><img decoding="async" src="/wp-content/uploads/2023/01/careers-hero-welder-1024x410.jpg" alt="Welder working on an industrial boiler"></figure>
<h2>Which code governs the weld?</h2>
<p>The equipment decides the construction code, and the code decides the certificate the manufacturer needs. Three other sections of the ASME Boiler and Pressure Vessel Code support all of them: Section II for materials, Section V for nondestructive examination methods, and Section IX for welding qualifications.</p>
<table>
<thead>
<tr>
<th>Equipment</th>
<th>Code</th>
<th>Certificate</th>
</tr>
</thead>
<tbody>
<tr>
<td>Power boilers: steam above 15 psig, or hot water above 160 psig or 250°F</td>
<td>ASME Section I</td>
<td>ASME S</td>
</tr>
<tr>
<td>Heating boilers: steam at 15 psig or less, hot water at 160 psig or less and 250°F or less</td>
<td>ASME Section IV</td>
<td>ASME H</td>
</tr>
<tr>
<td>Miniature boilers</td>
<td>ASME Section I</td>
<td>ASME M</td>
</tr>
<tr>
<td>Pressure vessels: blowdown separators, receivers, tanks</td>
<td>ASME Section VIII, Division 1</td>
<td>ASME U</td>
</tr>
<tr>
<td>Repairs and alterations to equipment in service</td>
<td>NBIC Part 3</td>
<td>National Board R</td>
</tr>
</tbody>
</table>
<h2>How are welding procedures and welders qualified?</h2>
<p>Section IX separates the procedure from the person.</p>
<ul>
<li>Welding Procedure Specification (WPS): the written instructions for a weld. It lists the process, base metal and filler metal groups, thickness range, positions, preheat and interpass temperature, postweld heat treatment, and electrical settings.</li>
<li>Procedure Qualification Record (PQR): the record of a test coupon welded to that procedure and then tested, typically by tension and bend tests, to prove the procedure produces sound metal with the required strength and ductility.</li>
<li>Welder Performance Qualification (WPQ): proof that a specific welder can make a sound weld with that process, by bend test or radiography. A welder&#8217;s qualification lapses if the welder goes six months without using the process.</li>
</ul>
<p>Changing an essential variable, such as the base metal group, the process, or a preheat or heat treatment requirement, means the procedure has to be requalified. That is why a shop cannot simply pick up a new material or process for a pressure part without first qualifying it.</p>
<p>The common processes are shielded metal arc (stick), gas tungsten arc (TIG) for root passes and tube work, gas metal and flux-cored arc for production welding, and submerged arc for long seams on heavy plate.</p>
<h2>What makes a pressure weld different?</h2>
<p>Materials come from Section II, with material test reports traceable to each plate, tube, and pipe. Typical firetube boiler materials are SA-516 Grade 70 plate for shells and tubesheets, SA-178 or SA-192 tube, and SA-106 pipe.</p>
<p>Joint design follows the construction code. Longitudinal and circumferential seams on shells are full penetration butt welds. Nozzles and openings have their own attachment and reinforcement rules. Fire tubes are expanded into the tubesheets and then beaded, seal welded, or both, to match the boiler&#8217;s design.</p>
<p>Heat control matters. Preheat slows cooling and drives off moisture, which reduces the risk of hydrogen cracking in thick sections, and low-hydrogen electrodes are kept dry in ovens. Postweld heat treatment relieves residual stress, and the construction code requires it above set thicknesses for each material group. Welding sequence and fixturing control distortion, so heads, tubesheets, and shells stay in alignment.</p>
<figure><img decoding="async" src="/wp-content/uploads/2026/10/mckenna-code-repair-tubesheet-welding.webp" alt="Welding at a firetube boiler tubesheet"></figure>
<h2>How are welds examined and accepted?</h2>
<ul>
<li>Visual examination of every weld, for cracks, undercut, porosity, lack of fusion at the surface, and alignment.</li>
<li>Radiographic (RT) or ultrasonic (UT) examination of butt welds where the code requires it, to find internal defects. Under Section VIII, Division 1, the extent of radiography sets the joint efficiency used in the thickness calculation: 1.00 for full radiography of a double-welded butt joint, 0.85 for spot, and 0.70 for none.</li>
<li>Magnetic particle (MT) or liquid penetrant (PT) examination for surface and near-surface cracks, where the code or the procedure calls for it.</li>
<li>A hydrostatic test of the finished vessel. Section I sets it at 1.5 times the maximum allowable working pressure, and Section VIII, Division 1 at 1.3 times, with a stress ratio adjustment.</li>
</ul>
<p>An Authorized Inspector from an Authorized Inspection Agency monitors the manufacturer&#8217;s quality control program, reviews the work, witnesses the hydrostatic test, and signs the Manufacturer&#8217;s Data Report. The nameplate is then stamped, and the boiler or vessel is registered with the National Board where the jurisdiction or the owner requires it.</p>
<h2>How do weld repairs work on a boiler in service?</h2>
<p>Weld repairs and alterations to pressure-retaining parts of a boiler in service are made under NBIC Part 3 by an organization holding a National Board R certificate. In most cases, replacing rolled and beaded tubes is not an R stamp repair; check with your Authorized Inspector. The Authorized Inspector is involved before the work starts, accepts the repair method, inspects the finished work, decides whether a pressure test is needed, and signs the form. Repairs are documented on Form R-1 and alterations on Form R-2. In California, Cal/OSHA is the jurisdiction.</p>
<p>Typical weld repairs include replacing seal-welded tubes, patches in a furnace or shell, building up wasted areas on a tubesheet, and replacing nozzles. Each uses a qualified WPS and qualified welders, the same as new construction. McKenna makes <a href="/services/r-stamp-repair/">code repairs under its National Board R certificate</a>, including <a href="/services/boiler-retubes/">retubes that involve welding</a>, on boilers and pressure vessels from any manufacturer.</p>
<h2>What to check before anyone welds on your boiler</h2>
<ul>
<li>Ask for the firm&#8217;s National Board R certificate, its number, and its expiration date.</li>
<li>Confirm the Authorized Inspector has been notified and has accepted the repair before work starts.</li>
<li>Ask which WPS will be used and confirm the welders are qualified to it.</li>
<li>Make the boiler safe: cooled, depressurized, drained, and isolated, with lockout/tagout on fuel, electrical, and water. Follow your site&#8217;s hot work and confined space procedures, and ventilate the furnace for welding inside it.</li>
<li>After the repair, get a copy of the signed R-1 or R-2 and keep it with the boiler records and the original data report.</li>
<li>Do not allow welding on a pressure part outside the code, whatever the schedule pressure. Let your inspector and insurer know about the repair as they require.</li>
</ul>
<figure class="wp-block-embed is-type-video is-provider-youtube"><iframe loading="lazy" width="560" height="315" src="https://www.youtube.com/embed/5M9I_bBrnZ0" title="McKenna Boiler Works welding video" frameborder="0" allow="accelerometer; autoplay; clipboard-write; encrypted-media; gyroscope; picture-in-picture; web-share" referrerpolicy="strict-origin-when-cross-origin" allowfullscreen></iframe></figure>
<h2>Common questions</h2>
<h3>Can a certified welder repair my boiler without an R certificate?</h3>
<p>Welder qualification covers the person. A code repair also needs a firm with a National Board R certificate, a qualified procedure, and an Authorized Inspector who accepts the work. Without those, the repair is outside the NBIC.</p>
<h3>What is the difference between a repair and an alteration?</h3>
<p>A repair restores the boiler or vessel to its original design. An alteration changes the design, such as the pressure rating, and needs engineering and the inspector&#8217;s acceptance before work begins. Repairs go on Form R-1 and alterations on Form R-2.</p>
<h3>What is a seal weld on a boiler tube?</h3>
<p>A seal weld is a small weld around the tube end at the tubesheet that makes the joint leak-tight. The tube is expanded into the tubesheet for strength, and the boiler&#8217;s design and code of construction set whether the end is beaded, seal welded, or both.</p>
<h3>Does every weld repair need a hydrostatic test?</h3>
<p>Not always. Under NBIC Part 3, the Authorized Inspector decides whether a pressure test is needed and at what pressure, based on the repair. Alterations generally need one.</p>
<h3>What do ASME S, H, M, and U mean?</h3>
<p>They are ASME certificates to build to the code: S for power boilers, H for heating boilers, M for miniature boilers, and U for pressure vessels. McKenna Boiler Works, Inc. holds all four, plus a National Board R certificate for repairs and alterations.</p>
<p>For a weld repair on a boiler or pressure vessel, see <a href="/services/r-stamp-repair/">code repairs</a> or call (323) 987-1816. For new construction, see <a href="/equipment/firetube-boilers/">McKenna firetube boilers</a>.</p>
<p>The post <a href="https://www.mckennaboiler.com/boilers/welding-the-critical-role-it-plays-in-pressure-vessel-and-industrial-boiler-fabrication/">Welding Boilers and Pressure Vessels to Code</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>Fall Boiler Maintenance: Getting Ready for Heating Season</title>
		<link>https://www.mckennaboiler.com/boiler-repair/october-boiler-maintenance-why-fall-is-the-right-time-to-service-your-industrial-boiler/</link>
		
		<dc:creator><![CDATA[McKenna Boiler Team]]></dc:creator>
		<pubDate>Mon, 31 Aug 2026 18:32:07 +0000</pubDate>
				<category><![CDATA[Boiler Maintenance]]></category>
		<category><![CDATA[Boiler Repair]]></category>
		<guid isPermaLink="false">https://www.mckennaboiler.com/?p=517264</guid>

					<description><![CDATA[<p>Fall is when a boiler that ran lightly all summer goes back to long runs at high fire. Here is why problems show up then, and the readiness work to do before the heating and process load peaks.</p>
<p>The post <a href="https://www.mckennaboiler.com/boiler-repair/october-boiler-maintenance-why-fall-is-the-right-time-to-service-your-industrial-boiler/">Fall Boiler Maintenance: Getting Ready for Heating Season</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></description>
										<content:encoded><![CDATA[<p>Fall is when a boiler that ran lightly all summer goes back to long runs at high fire, and problems that stayed hidden at low load show up: a burner tuned at low fire that smokes or trips at high fire, a low water cutoff that has filled with sludge, a standby boiler that has not fired in months. This guide from McKenna Boiler Works, Inc. covers the readiness work to do in September and early October, before the heating and process load climbs, so the boiler&#8217;s first hard day of the season is not its first test.</p>
<figure class="wp-block-image size-large"><img loading="lazy" decoding="async" width="1024" height="547" src="/wp-content/uploads/2026/08/emergency-boiler-corrosion-repair-1024x547.jpg" alt="Corrosion found during an industrial boiler repair" class="wp-image-517265" srcset="https://www.mckennaboiler.com/wp-content/uploads/2026/08/emergency-boiler-corrosion-repair-1024x547.jpg 1024w, https://www.mckennaboiler.com/wp-content/uploads/2026/08/emergency-boiler-corrosion-repair-300x160.jpg 300w, https://www.mckennaboiler.com/wp-content/uploads/2026/08/emergency-boiler-corrosion-repair-768x410.jpg 768w, https://www.mckennaboiler.com/wp-content/uploads/2026/08/emergency-boiler-corrosion-repair-1536x821.jpg 1536w, https://www.mckennaboiler.com/wp-content/uploads/2026/08/emergency-boiler-corrosion-repair-700x374.jpg 700w, https://www.mckennaboiler.com/wp-content/uploads/2026/08/emergency-boiler-corrosion-repair.jpg 1716w" sizes="(max-width: 1024px) 100vw, 1024px" /></figure>
<h2>Why do problems show up when the load rises?</h2>
<p>At low load a firetube boiler fires briefly or modulates near low fire. Tube sheet and tube-end temperatures stay moderate, the feedwater pump runs occasionally, and a marginal control has few chances to fail. At high load the burner runs near the top of its range for hours. Combustion settings that were never checked at high fire matter now, because the fuel and air curve is set point by point and drift at one end does not show at the other. Heat flux through the tubes and furnace rises, so any scale on the water side raises metal temperature more than it did in July. Feedwater demand rises too, which tests pumps, check valves, and makeup water softeners. A boiler that ran fine in summer can therefore trip, smoke, or leak in October without anything having broken over the season.</p>
<h2>How do you bring an idle or standby boiler back into service?</h2>
<p>Many plants run one boiler through the summer and keep a second in layup. Bringing it back takes care, because a boiler stored wrong can pit badly in a few months.</p>
<ul>
<li><strong>Wet layup:</strong> the boiler was filled with treated water, often with extra oxygen scavenger and a raised pH. Follow the boiler manufacturer’s manual and your water treatment company’s instructions to drain or adjust it before firing.</li>
<li><strong>Dry layup:</strong> the boiler was drained, dried, and sealed, often with desiccant trays inside. Removing the trays means opening the boiler, so follow lockout/tagout and your confined space procedures, and account for every tray before it is closed up. Fill with treated water per the program.</li>
<li><strong>Warm-up:</strong> fire at low fire and bring the boiler up to pressure slowly, as the manufacturer specifies. A fast cold start puts thermal stress on tube ends, tube sheets, and refractory.</li>
<li><strong>Controls:</strong> before the boiler goes on line, test its low water cutoffs and flame safeguard. A standby boiler that cannot start on demand is not a standby.</li>
</ul>
<h2>What should be tested and tuned before the peak?</h2>
<p>Combustion should be checked across the whole firing range, low fire to high fire, with an analyzer reading O2, CO, and NOx where the permit requires it. Air district limits apply at every rate: South Coast AQMD Rules 1146, 1146.1, and 1146.2, San Joaquin Valley Rules 4306 and 4320, and Bay Area Regulation 9, Rule 7 each set NOx and CO limits by unit size, and your permit may require periodic portable analyzer checks or source tests. A retune after any burner, linkage, or control change keeps the boiler inside those limits. See <a href="/services/combustion-tuning/">combustion tuning</a>.</p>
<p>Safety controls under ASME CSD-1 (automatically fired boilers up to 12.5 million Btu per hour input) or NFPA 85 (larger units) should be tested and logged: primary and auxiliary low water cutoffs, operating and high limit controls, flame safeguard and scanner, fuel valve proving, and air and gas pressure switches. On steam systems, check steam traps before the heating season, since a failed-open trap wastes steam and a failed-closed trap floods heat exchangers and causes water hammer. A <a href="/services/steam-trap-audits/">steam trap audit</a> finds both.</p>
<h2>What about inspections, permits, and parts?</h2>
<p>If your power boiler&#8217;s Cal/OSHA permit to operate expires during the winter, schedule the inspection now. Power boilers (steam above 15 psig) are inspected internally and externally at least once a year under Labor Code 7682, and the internal inspection needs the boiler cold and open, which is much easier to arrange before the load peaks. Your water treatment company should be on site for the internal inspection to check the water side.</p>
<p>Check your spare parts against common failures that stop a boiler: flame scanner, igniter or pilot assembly, low water cutoff switch or probe, gauge glass and gaskets, handhole and manway gaskets, and fuses for the control circuit. If your gas service is interruptible, test the backup fuel system and confirm fuel on hand before the first curtailment notice.</p>
<h2>What to do: fall readiness checklist</h2>
<ol>
<li>Review last season&#8217;s inspection report and service findings; confirm each deficiency was repaired.</li>
<li>Bring standby boilers out of layup per the boiler manufacturer&#8217;s manual and your water treatment company&#8217;s instructions, and fire them.</li>
<li>Test low water cutoffs on every boiler. If the burner does not stop when the cutoff should trip, shut the burner off manually and call for service.</li>
<li>Test the flame safeguard. If it does not lock out on flame failure, shut the boiler down and call for service.</li>
<li>Have combustion checked and tuned at low, mid, and high fire against the air permit limits.</li>
<li>Inspect steam traps, condensate return, and the feedwater pumps.</li>
<li>Confirm the Cal/OSHA permit date and book the inspection if it falls in winter.</li>
<li>Stock the common spare parts and test backup fuel if your gas service is interruptible.</li>
<li>Follow lockout/tagout and the manufacturer&#8217;s instructions for every task that opens the boiler, fuel train, or electrical panel.</li>
</ol>
<h2>Common questions</h2>
<h3>Is October too late for boiler maintenance?</h3>
<p>Not for readiness checks, tuning, and control testing, which can be done with the boiler in service or briefly off line. Major work that needs the boiler cold and open, such as retubes or refractory repair, is best done during the summer low-load window. If major work is found now, plan it with a rental or a second boiler covering the load.</p>
<h3>Why retune a boiler that was tuned last spring?</h3>
<p>Linkages wear, air temperature and density change with the season, and gas supply pressure varies. A burner set in warm weather can run lean or rich when the combustion air is colder. Checking the curve at every firing rate before the peak keeps the boiler efficient and inside its permit limits.</p>
<h3>How should a standby boiler be kept ready during winter?</h3>
<p>Keep it in the layup the boiler manufacturer’s manual and your water treatment company specify, test its controls on a schedule, and fire it periodically so you know it starts. Some plants keep it warm through a heating coil or by rotating boilers weekly. Whatever the method, log it.</p>
<h3>What if a boiler fails in the middle of the season?</h3>
<p>Make it safe first: burner off, no feedwater added to a boiler that ran low, lockout per your site&#8217;s procedures. Then call for service. A rental boiler can carry the load if the repair will take time; see <a href="/services/emergency-services/">emergency boiler service</a>.</p>
<h3>Does McKenna service other manufacturers&#8217; boilers?</h3>
<p>Yes. McKenna services and repairs boilers from other manufacturers and installs, sets up, and tunes burners and controls from any manufacturer.</p>
<h2>Scheduling fall service</h2>
<p>To book fall readiness work, see <a href="/services/preventative-maintenance/">preventative maintenance</a> or call (323) 987-1816. A live person answers 24/7.</p>
<p>The post <a href="https://www.mckennaboiler.com/boiler-repair/october-boiler-maintenance-why-fall-is-the-right-time-to-service-your-industrial-boiler/">Fall Boiler Maintenance: Getting Ready for Heating Season</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>McKenna Boiler Works History: 1921 to Today</title>
		<link>https://www.mckennaboiler.com/boilers/mckenna-boiler-works-a-century-of-steam-innovation-and-trust-from-the-1920s-to-today/</link>
		
		<dc:creator><![CDATA[McKenna Boiler Team]]></dc:creator>
		<pubDate>Fri, 31 Jul 2026 20:54:08 +0000</pubDate>
				<category><![CDATA[Boilers]]></category>
		<guid isPermaLink="false">https://www.mckennaboiler.com/?p=517260</guid>

					<description><![CDATA[<p>McKenna Boiler Works, Inc. has built boilers since 1921, and its roots go back to 1887 in Los Angeles. Here is the documented history, what McKenna's code certificates mean, and what it builds and services today.</p>
<p>The post <a href="https://www.mckennaboiler.com/boilers/mckenna-boiler-works-a-century-of-steam-innovation-and-trust-from-the-1920s-to-today/">McKenna Boiler Works History: 1921 to Today</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></description>
										<content:encoded><![CDATA[<p>McKenna Boiler Works, Inc. is a fifth-generation, family-owned company founded in 1921, and its roots go back to 1887, when J.B. McKenna was servicing boilers in Los Angeles. Today McKenna designs, builds, installs, and services industrial firetube, firebox, and vertical boilers, feedwater systems, blowdown tanks and separators, and ASME tanks and vessels, built in its shop in California, and it services and repairs boilers from other manufacturers too. This page covers what is documented about that history and what it means for a plant engineer choosing a boiler company now.</p>
<figure class="wp-block-image size-full"><img loading="lazy" decoding="async" width="500" height="282" src="/wp-content/uploads/2024/09/commercial-boiler-company-products-mobile.jpg" alt="McKenna industrial boilers" class="wp-image-17442" srcset="https://www.mckennaboiler.com/wp-content/uploads/2024/09/commercial-boiler-company-products-mobile.jpg 500w, https://www.mckennaboiler.com/wp-content/uploads/2024/09/commercial-boiler-company-products-mobile-300x169.jpg 300w" sizes="(max-width: 500px) 100vw, 500px" /></figure>
<h2>Where did McKenna start?</h2>
<p>J.B. McKenna was servicing boilers in Los Angeles from 1887, and the company was founded in 1921. McKenna is family-owned and now in its fifth generation. McKenna still serves Los Angeles; the shop where equipment is built and parts ship from is at 2601 Industry Street, Oceanside, CA 92054.</p>
<p>McKenna both builds boilers and services them. That matters for one practical reason: the people who design and weld a boiler also see how boilers fail in service, and the people who service boilers in the field know what was built well and what was not.</p>
<h2>What has changed in industrial boilers since 1921?</h2>
<p>Three changes shaped every boiler built since McKenna started building them.</p>
<ul>
<li><strong>Construction codes.</strong> The first edition of the ASME Boiler Code was dated 1914 and published in 1915, after a series of deadly boiler explosions in the United States. The National Board of Boiler and Pressure Vessel Inspectors was organized in 1919 so that states could adopt one standard and inspect to it. Today ASME Section I covers power boilers, Section IV heating boilers, and Section VIII pressure vessels, and repairs and alterations in service follow the National Board Inspection Code (NBIC). In California, Cal/OSHA&#8217;s Boiler and Fired Pressure Vessel Safety Orders (Title 8) govern inspection and the permit to operate.</li>
<li><strong>Emissions limits.</strong> California&#8217;s air districts set strict NOx limits for boilers. South Coast AQMD Rules 1146, 1146.1, and 1146.2, San Joaquin Valley Rules 4306 and 4320, and Bay Area Regulation 9, Rule 7 apply by unit size, and a new boiler&#8217;s burner has to be matched to the limit where it will run.</li>
<li><strong>Controls.</strong> Mechanical linkages that set fuel and air together have given way to parallel positioning, with separate servo motors on fuel and air, O2 trim, and burner management systems built to ASME CSD-1 or NFPA 85. These hold combustion closer to the setpoint across the firing range and make it easier to stay inside a permit limit.</li>
</ul>
<h2>What do McKenna&#8217;s code certificates mean?</h2>
<p>A certificate tells you what kind of code work a company is authorized to do. McKenna holds these:</p>
<table>
<thead>
<tr>
<th>Certificate</th>
<th>Issued by</th>
<th>What it covers</th>
</tr>
</thead>
<tbody>
<tr>
<td>S</td>
<td>ASME</td>
<td>Power boilers built to Section I (steam above 15 psig)</td>
</tr>
<tr>
<td>H</td>
<td>ASME</td>
<td>Heating boilers built to Section IV (steam up to 15 psig, hot water up to 160 psig and 250°F)</td>
</tr>
<tr>
<td>M</td>
<td>ASME</td>
<td>Miniature boilers built to Section I</td>
</tr>
<tr>
<td>U</td>
<td>ASME</td>
<td>Pressure vessels built to Section VIII, Division 1</td>
</tr>
<tr>
<td>R (No. 11037)</td>
<td>National Board</td>
<td>Repairs and alterations to boilers and pressure vessels under the NBIC</td>
</tr>
</tbody>
</table>
<p>McKenna maintains a written quality control manual for its code work. Under each certificate, an Authorized Inspector reviews code work and signs the data report for new construction or accepts repairs.</p>
<h2>What does McKenna build and service today?</h2>
<p>McKenna builds <a href="/equipment/firetube-boilers/">firetube boilers</a>, firebox boilers, and vertical boilers, plus feedwater systems, blowdown tanks and separators, and ASME tanks and vessels. Each can be a standard model or custom-designed to the customer&#8217;s specifications and to fit a specific room or footprint. New McKenna boilers come with Autoflame controls as a standard option and a burner matched to the boiler and the emissions limit where it will run. An electric boiler is in development; there is no release date.</p>
<p>On the service side, McKenna is a factory-authorized Autoflame Tech Center and Limpsfield Burner Tech Center, and it installs, sets up, and tunes burners and controls from any manufacturer, including a brand an engineer or contractor has already specified. Limpsfield, Autoflame, and Power Flame are what McKenna can recommend, but they are not the only options. McKenna also keeps rental boilers, some of which carry South Coast AQMD permits, and makes code repairs on boilers and pressure vessels from any manufacturer under its National Board R certificate.</p>
<p>McKenna serves Los Angeles and all of California, and does startup and initial commissioning in any state.</p>
<h2>What to check when choosing a boiler company</h2>
<p>Age alone does not tell you whether a boiler company can do your job. Ask these questions of McKenna or of anyone else:</p>
<ol>
<li>Which ASME certificates does the shop hold, and do they match the boiler or vessel you need (S for Section I, H for Section IV, U for Section VIII)?</li>
<li>Does the service company hold a National Board R certificate for repairs to pressure parts? Ask for the number.</li>
<li>What is the company&#8217;s California contractor license? McKenna&#8217;s is CA Lic. #1044490.</li>
<li>Who does startup, commissioning, and combustion tuning, and will they tune to your air permit limit?</li>
<li>Who answers the phone at 2 a.m.?</li>
<li>Will the company work on the other manufacturers&#8217; equipment you already have?</li>
</ol>
<p>McKenna is not always the lowest price. The reason to choose it is one accountable company that designs, builds, installs, and services the boiler.</p>
<h2>Common questions</h2>
<h3>When was McKenna Boiler Works, Inc. founded?</h3>
<p>McKenna Boiler Works, Inc. was founded in 1921. Its roots go back to 1887, when J.B. McKenna was servicing boilers in Los Angeles. The company is family-owned and now in its fifth generation.</p>
<h3>Where are McKenna boilers built?</h3>
<p>McKenna boilers are built in California, in McKenna&#8217;s shop at 2601 Industry Street, Oceanside, CA 92054. Parts also ship from that shop.</p>
<h3>Does McKenna only work on McKenna boilers?</h3>
<p>No. McKenna services and repairs boilers from other manufacturers, makes code repairs on boilers and pressure vessels from any manufacturer under its National Board R certificate, and installs and tunes burners and controls from any manufacturer.</p>
<h3>Does McKenna make electric boilers?</h3>
<p>An electric boiler is in development. There is no release date yet.</p>
<h3>What area does McKenna serve?</h3>
<p>McKenna serves Los Angeles and all of California. McKenna also does startup and initial commissioning in any state.</p>
<h2>Talking to McKenna</h2>
<p>For a new boiler, a repair, or a <a href="/services/installation/">turnkey installation</a>, call (323) 987-1816 or use the <a href="/contact-us/">contact form</a>. Code repairs are covered on the <a href="/services/r-stamp-repair/">R certificate repair</a> page.</p>
<p>The post <a href="https://www.mckennaboiler.com/boilers/mckenna-boiler-works-a-century-of-steam-innovation-and-trust-from-the-1920s-to-today/">McKenna Boiler Works History: 1921 to Today</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>Types of Industrial Boilers Compared: Which Fits Your Load?</title>
		<link>https://www.mckennaboiler.com/boilers/comparing-and-contrasting-the-different-types-of-industrial-boilers/</link>
		
		<dc:creator><![CDATA[McKenna Boiler Team]]></dc:creator>
		<pubDate>Tue, 07 Jul 2026 17:45:53 +0000</pubDate>
				<category><![CDATA[Boilers]]></category>
		<guid isPermaLink="false">https://www.mckennaboiler.com/?p=517253</guid>

					<description><![CDATA[<p>Firetube, firebox, vertical, watertube, condensing, and electric boilers each fit a different load. This comparison covers the code limits, how each handles load swings, and the questions to answer before choosing.</p>
<p>The post <a href="https://www.mckennaboiler.com/boilers/comparing-and-contrasting-the-different-types-of-industrial-boilers/">Types of Industrial Boilers Compared: Which Fits Your Load?</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></description>
										<content:encoded><![CDATA[<p>The right industrial boiler depends on four things: steam or hot water, the pressure or temperature you need, how the load swings, and the room you have to put it in. Firetube boilers fit most industrial and commercial steam and hot water loads; firebox and vertical boilers fit smaller loads and tight spaces; watertube boilers take over at very high pressures and capacities; condensing and electric boilers fit narrower cases. McKenna Boiler Works, Inc. builds firetube, firebox, and vertical boilers, and this comparison explains where each type fits and where it does not.</p>
<figure class="wp-block-image size-full"><img loading="lazy" decoding="async" width="600" height="861" src="/wp-content/uploads/2024/09/industrial-boiler-pressure-vessel-los-angeles.jpg" alt="Industrial firetube boiler pressure vessel" class="wp-image-17236" srcset="https://www.mckennaboiler.com/wp-content/uploads/2024/09/industrial-boiler-pressure-vessel-los-angeles.jpg 600w, https://www.mckennaboiler.com/wp-content/uploads/2024/09/industrial-boiler-pressure-vessel-los-angeles-209x300.jpg 209w" sizes="(max-width: 600px) 100vw, 600px" /></figure>
<h2>Which code applies: Section I or Section IV?</h2>
<p>Before choosing a type, settle the pressure class, because it sets the construction code, the inspection rules, and often the operator requirements. ASME Section IV covers heating boilers: steam at 15 psig or less, and hot water at 160 psig or less and 250°F or less. Anything above those limits is a power boiler built to ASME Section I. In California, steam power boilers (above 15 psig) are inspected internally and externally at least once a year by Cal/OSHA or an insurance inspector under Labor Code 7682 and need a permit to operate; low-pressure boilers are exempt from the annual inspection and permit under 8 CCR 771 if their required controls are fitted and maintained.</p>
<p>Most process loads (sterilizers, jacketed kettles, presses, laundry ironers) need steam above 15 psig because they need temperature. Saturated steam at 15 psig is about 250°F; at 100 psig it is about 338°F; at 150 psig about 366°F. Building heat and many domestic hot water systems run at low pressure.</p>
<h2>How do the main types compare?</h2>
<table>
<thead>
<tr>
<th>Type</th>
<th>How it works</th>
<th>Fits</th>
<th>Limits</th>
</tr>
</thead>
<tbody>
<tr>
<td><a href="/equipment/firetube-boilers/">Firetube</a></td>
<td>Combustion gas passes through a furnace tube and then through tubes surrounded by water in a horizontal shell</td>
<td>Low and high pressure steam and hot water; plants with load swings</td>
<td>Slower cold start; shell size limits practical pressure and capacity</td>
</tr>
<tr>
<td><a href="/equipment/firebox-boilers/">Firebox</a></td>
<td>A firetube design with a box-shaped combustion chamber</td>
<td>Smaller steam and hot water loads, often low pressure heating</td>
<td>Smaller capacities than a full firetube</td>
</tr>
<tr>
<td><a href="/equipment/vertical-boilers/">Vertical</a></td>
<td>Vertical shell with tubes or a furnace inside it, standing on end</td>
<td>Small loads, tight floor space, fast warm-up</td>
<td>Small sizes; less water stored for sudden loads</td>
</tr>
<tr>
<td>Watertube</td>
<td>Water flows inside tubes; combustion gas flows around them</td>
<td>Very high pressures, large capacities, superheated steam</td>
<td>Higher cost, tighter water chemistry, more complex to inspect</td>
</tr>
<tr>
<td>Condensing hot water</td>
<td>Flue gas cooled below its dew point to recover latent heat</td>
<td>Hot water systems with cool return water</td>
<td>Hot water only; gains disappear with hot return water; acidic condensate</td>
</tr>
<tr>
<td>Electric</td>
<td>Resistance elements or electrodes heat the water</td>
<td>Sites with ample electrical service and strict combustion limits</td>
<td>Operating cost depends on electric rates; needs large electrical service</td>
</tr>
</tbody>
</table>
<h2>Why does water content matter for load swings?</h2>
<p>A firetube boiler holds a large volume of water at saturation temperature. When a big load opens up, such as a batch sterilizer or a cook kettle coming on, pressure drops slightly and some of that stored water flashes to steam, carrying the load for the seconds to minutes it takes the burner to fire up. That stored energy is why firetube boilers ride swings well and hold steady pressure. A watertube or vertical boiler with less water reacts faster to burner changes but has less in reserve, so the controls have to respond more quickly to keep pressure from sagging and to keep water level from shrinking and swelling enough to trip a cutoff. The tradeoff is a slower cold start for the firetube: more water and more steel have to come up to temperature, and the warm-up has to be gradual to protect tube ends and refractory.</p>
<h2>When do condensing and electric boilers make sense?</h2>
<p>A condensing boiler recovers latent heat only when the flue gas cools below its dew point, which for natural gas is roughly 130°F. That needs return water well below that temperature, so condensing boilers suit low-temperature hot water heating. They do not make steam, and with hot return water they perform like a conventional boiler. Their condensate is acidic and usually needs neutralizing before it reaches the drain.</p>
<p>An electric boiler has no burner, no stack, and no on-site combustion emissions, which is the reason plants look at one under tight air district limits. Nearly all the electric energy ends up in the water, but the comparison that matters is cost per unit of heat delivered. One therm is 100,000 Btu, about 29.3 kWh, so compare the price of 29.3 kWh against the price of one therm divided by your gas boiler&#8217;s efficiency. Electrical service capacity is often the deciding constraint. McKenna&#8217;s electric boiler is in development, with no release date.</p>
<h2>What to answer before choosing a boiler</h2>
<ol>
<li><strong>Load:</strong> peak and minimum, in lb/hr of steam, boiler horsepower, or MBH. Fuel meter data from the existing boiler is the most direct source. The <a href="/equipment/boiler-sizing-calculator/">boiler sizing calculator</a> converts units.</li>
<li><strong>Pressure or temperature:</strong> the highest steam pressure or water temperature any user needs.</li>
<li><strong>Load profile:</strong> steady, daily cycles, or sudden batch loads.</li>
<li><strong>Redundancy:</strong> whether the plant can tolerate one boiler down. Two boilers sized for the load often beat one large one.</li>
<li><strong>Space:</strong> room footprint, door and rigging path, ceiling height, and tube-pull clearance for a firetube.</li>
<li><strong>Fuel and electrical service:</strong> gas supply pressure and capacity at full fire, and available electrical capacity.</li>
<li><strong>Air district limit:</strong> the NOx and CO limits for the unit size under South Coast AQMD Rules 1146, 1146.1, and 1146.2, San Joaquin Valley Rules 4306 and 4320, Bay Area Regulation 9, Rule 7, or your district&#8217;s rule.</li>
</ol>
<h2>Common questions</h2>
<h3>What is the most common industrial boiler type?</h3>
<p>For industrial and commercial steam and hot water loads, the firetube boiler is the most common type. It is simple to operate, inspect, and retube, and its large water volume handles load swings well. Watertube boilers take over at very high pressures and capacities.</p>
<h3>Is a watertube boiler more efficient than a firetube boiler?</h3>
<p>Not inherently. Efficiency depends mostly on combustion tuning, stack temperature, and whether heat recovery is fitted. Watertube boilers are chosen for higher pressures and capacities.</p>
<h3>Can a boiler be built to fit an existing room?</h3>
<p>Yes. McKenna builds standard models or custom-designs firetube, firebox, and vertical boilers to the customer&#8217;s specifications and to fit a specific room or footprint. Measure the rigging path and tube-pull clearance before you choose.</p>
<h3>Should a plant have one boiler or two?</h3>
<p>Two boilers sized for the load let one be serviced or inspected while the other runs, and a smaller boiler at low load cycles less. One boiler costs less up front but needs a rental for every outage. The answer depends on how much downtime the plant can tolerate.</p>
<h3>Does McKenna work on boiler types it does not build?</h3>
<p>Yes. McKenna services and repairs boilers from other manufacturers, makes code repairs on boilers and pressure vessels from any manufacturer, and installs and tunes burners and controls from any manufacturer.</p>
<h2>Choosing the right boiler</h2>
<p>To size and select a boiler or plan a <a href="/services/boiler-replacement/">boiler replacement</a>, call McKenna at (323) 987-1816.</p>
<p>The post <a href="https://www.mckennaboiler.com/boilers/comparing-and-contrasting-the-different-types-of-industrial-boilers/">Types of Industrial Boilers Compared: Which Fits Your Load?</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>How Industrial Boilers Get Damaged</title>
		<link>https://www.mckennaboiler.com/boiler-maintenance/industrial-boiler-damage-susceptibility/</link>
		
		<dc:creator><![CDATA[McKenna Boiler Team]]></dc:creator>
		<pubDate>Wed, 20 May 2026 21:43:01 +0000</pubDate>
				<category><![CDATA[Boiler Maintenance]]></category>
		<category><![CDATA[Boiler Repair]]></category>
		<guid isPermaLink="false">https://www.mckennaboiler.com/?p=517248</guid>

					<description><![CDATA[<p>Industrial boilers are damaged in a handful of predictable ways, from oxygen pitting to low-water overheating. This post explains each mechanism, where it shows up on a firetube boiler, and how inspection finds it early.</p>
<p>The post <a href="https://www.mckennaboiler.com/boiler-maintenance/industrial-boiler-damage-susceptibility/">How Industrial Boilers Get Damaged</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></description>
										<content:encoded><![CDATA[<p>Industrial boilers are damaged in a handful of predictable ways: corrosion from oxygen or acid in the water, overheating from scale or low water, cracking from repeated heating and cooling, and corrosion on the fire side when flue gas condenses. Each leaves recognizable signs, and most are found during the internal inspection long before a tube or plate fails. McKenna Boiler Works, Inc. repairs this damage on its own and other manufacturers&#8217; boilers, and this post explains how each mechanism works, where it shows up on a firetube boiler, and how it is caught.</p>
<figure class="wp-block-image size-full"><img loading="lazy" decoding="async" width="1000" height="771" src="/wp-content/uploads/2026/05/boiler-corrosion-repair-los-angeles.jpg" alt="Corrosion on industrial boiler surfaces" class="wp-image-517249" srcset="https://www.mckennaboiler.com/wp-content/uploads/2026/05/boiler-corrosion-repair-los-angeles.jpg 1000w, https://www.mckennaboiler.com/wp-content/uploads/2026/05/boiler-corrosion-repair-los-angeles-300x231.jpg 300w, https://www.mckennaboiler.com/wp-content/uploads/2026/05/boiler-corrosion-repair-los-angeles-768x592.jpg 768w, https://www.mckennaboiler.com/wp-content/uploads/2026/05/boiler-corrosion-repair-los-angeles-700x540.jpg 700w" sizes="(max-width: 1000px) 100vw, 1000px" /></figure>
<h2>How does water-side corrosion damage a boiler?</h2>
<p>Boiler steel survives in hot water because a thin, tight layer of magnetite (black iron oxide) forms on its surface and slows further corrosion. Most water-side damage starts where that layer is broken or attacked.</p>
<ul>
<li><strong>Oxygen pitting.</strong> Dissolved oxygen in feedwater attacks steel in small, deep pits, often capped with reddish tubercles. It shows up near where feedwater enters, in the feedwater tank and lines, and throughout a boiler left idle without proper layup. Oxygen is removed by heating the feedwater (a hot feedwater tank or a deaerator) and by an oxygen scavenger such as sulfite.</li>
<li><strong>Carbonic acid in condensate.</strong> Carbonate and bicarbonate in makeup water break down in the boiler and release carbon dioxide with the steam. When the steam condenses, the CO2 forms carbonic acid that thins condensate return piping, usually along the bottom of the pipe and at threads. Rust-colored condensate and leaking return lines are the sign.</li>
<li><strong>Caustic gouging.</strong> Under porous deposits, boiler water can concentrate as it boils off, building up enough caustic to dissolve the magnetite and the steel beneath it. The result is smooth, irregular gouges under deposits, often at the hottest surfaces.</li>
</ul>
<p>Your water treatment company sets the program that controls all three, including the chemical feed, test limits, and blowdown rate, within the limits in the boiler manufacturer’s manual. They should be on site when the boiler is opened for inspection to check and monitor the water side. McKenna is not a water treatment company.</p>
<h2>Why do scale and low water overheat the steel?</h2>
<p>Tube and furnace metal stays near water temperature only because water carries heat away from it. Scale (calcium, magnesium, and silica deposits from hard or poorly treated water) insulates the steel from the water, so the metal runs hotter for the same firing rate. The furnace tube and the first-pass tubes see the highest heat flux, so they overheat first. Steel loses strength as it heats, and an overheated furnace can bulge or an overheated tube can sag, leak, or rupture.</p>
<p>Low water is the extreme case. If the water level drops below the top of the furnace or tubes, that metal has nothing cooling it and can overheat within minutes. That is why the low water cutoffs exist, and why they must never be bypassed. If the water level is out of sight in the gauge glass, shut off the burner and do not add feedwater to a hot boiler: cold water on overheated steel can crack it or cause a violent release of steam. Leave the boiler off and call for service, and have it inspected before it is refilled.</p>
<h2>What causes cracking and leaking tube ends?</h2>
<p>Each time a boiler fires, cycles off, and fires again, the tubes, tube sheets, and furnace expand and contract by different amounts. Over thousands of cycles this thermal fatigue loosens rolled tube ends and starts cracks in the tube sheet ligaments between tube holes, most often at the rear tube sheet where gas temperature is highest. Short cycling from an oversized burner or a bad control setting multiplies the cycle count. So does a fast cold start. Scale on the tube sheet makes it worse by raising the metal temperature at the joint.</p>
<h2>What damages the fire side?</h2>
<p>When flue gas cools below its dew point, the water vapor condenses on the cooler surfaces near the end of the gas path, and the condensate is acidic. On natural gas this happens mostly during frequent cold starts and at very low stack temperatures; on fuel oil, sulfur in the fuel forms sulfuric acid and the damage is faster. Soot from poor combustion holds moisture and acid against the steel. Outside the boiler, wet insulation from a leak or a roof drip causes corrosion under insulation on the shell and piping, which is hidden until the insulation is removed. Good <a href="/services/combustion-tuning/">combustion tuning</a> and avoiding short cycling reduce fire-side damage.</p>
<h2>How is damage found before it fails?</h2>
<table>
<thead>
<tr>
<th>Method</th>
<th>What it finds</th>
<th>When it is done</th>
</tr>
</thead>
<tbody>
<tr>
<td>Internal visual inspection, water side</td>
<td>Scale, pitting, gouging, deposits, sludge</td>
<td>Annual internal inspection with the boiler open</td>
</tr>
<tr>
<td>Fire-side inspection</td>
<td>Soot, leaking or cracked tube ends, furnace distortion, refractory damage</td>
<td>Annual service and inspection</td>
</tr>
<tr>
<td>Ultrasonic thickness (UT) readings</td>
<td>Wall loss on shell, tube sheets, and accessible tubes</td>
<td>When the inspector requests it, or to plan a retube or repair</td>
</tr>
<tr>
<td>Hydrostatic test</td>
<td>Leaks at tube ends and repairs</td>
<td>After repairs, or when the inspector requires it</td>
</tr>
<tr>
<td>Operating log trends</td>
<td>Rising stack temperature, makeup water, or blowdown needs</td>
<td>Every shift</td>
</tr>
</tbody>
</table>
<p>In California, power boilers (steam above 15 psig) are inspected internally and externally at least once a year under Labor Code 7682. Welded repairs to pressure-retaining parts are made under the National Board Inspection Code (NBIC) Part 3 by an organization holding a National Board R certificate, with an Authorized Inspector accepting the work. In most cases, replacing rolled and beaded tubes is not an R stamp repair; check with your Authorized Inspector.</p>
<h2>What to do: preventing boiler damage</h2>
<ol>
<li>Follow your water treatment company&#8217;s program: daily tests, chemical feed, and surface and bottom blowdown at the rate they set, and never less often than the boiler manufacturer’s manual calls for.</li>
<li>Blow down the gauge glass and float-type low water cutoffs on the manufacturer&#8217;s schedule and confirm the burner stops. If a cutoff does not trip, shut the burner off manually and call for service.</li>
<li>If water is out of sight in the glass, shut off the burner, do not add feedwater, and call for service.</li>
<li>Warm the boiler slowly from cold, as the manufacturer specifies, and fix short cycling.</li>
<li>Have combustion tuned at least once a year and after any burner or control change.</li>
<li>Lay up idle boilers wet or dry, as the boiler manufacturer’s manual and your water treatment company specify.</li>
<li>Open the boiler for the annual internal inspection and fix what it finds. Follow lockout/tagout and confined space procedures before anyone opens or enters it.</li>
</ol>
<h2>Common questions</h2>
<h3>What is the most common cause of boiler tube failure?</h3>
<p>On firetube boilers, most tube failures trace to water-side problems (scale, oxygen pitting, or deposits that cause overheating) or to thermal fatigue at the tube ends. Low-water overheating causes the most severe failures. The internal inspection finds the early signs of each.</p>
<h3>Can a pitted boiler be repaired?</h3>
<p>Often. Depending on depth and location, pitted areas may be repaired by weld buildup or a patch under the NBIC, with an Authorized Inspector accepting the repair, or the tube may be replaced. Widespread pitting or thinning may make a <a href="/services/boiler-retubes/">retube</a> or replacement the better choice.</p>
<h3>Why does my boiler keep leaking at the tube ends?</h3>
<p>Repeated leaks at rolled tube ends usually point to thermal fatigue from cycling, scale on the tube sheet, or tube ends that have been re-rolled too many times. Re-rolling treats the symptom. Fixing the cycling and the water side, and replacing tubes where needed, treats the cause.</p>
<h3>Who decides whether a damaged boiler can return to service?</h3>
<p>The Authorized Inspector, under the NBIC, accepts code repairs, and Cal/OSHA issues the permit to operate for power boilers in California. The repair itself is made by an organization holding a National Board R certificate.</p>
<h3>Does McKenna repair other manufacturers&#8217; boilers?</h3>
<p>Yes. McKenna makes code repairs on boilers and pressure vessels from any manufacturer under its National Board R certificate No. 11037.</p>
<h2>Getting damage assessed</h2>
<p>For an inspection, repair, or retube, see <a href="/services/boiler-inspections-testing/">boiler inspections and testing</a> and <a href="/services/r-stamp-repair/">R certificate repairs</a>, or call (323) 987-1816.</p>
<p>The post <a href="https://www.mckennaboiler.com/boiler-maintenance/industrial-boiler-damage-susceptibility/">How Industrial Boilers Get Damaged</a> appeared first on <a href="https://www.mckennaboiler.com">McKenna Boiler</a>.</p>
]]></content:encoded>
					
		
		
			</item>
	</channel>
</rss>